6 Vector Control and Applied Functions
(2) Set the rated frequency of the motor in the 1st Base Frequency (A003) and set the
maximum frequency in the 1st Maximum Frequency (A004).
The rated/maximum frequency values can be calculated from the rated/maximum rotation
speed of the PM motor as follows:
(Maximum frequency) [Hz]
(3) Set the rated voltage of your PM motor in the 1st Motor Rated Voltage Selection
(A082) and set the rated current in the PM Motor Rated Current (H105).
The 1s Motor Rated Voltage Selection parameter must be set to the highest value closest to
the rated voltage of the motor.
In addition, for the purpose of overload protection, set the rated current of the PM motor in
the 1st Electronic Thermal Level (b012).
(4) In the PM Motor Parameter Ke (H109), set the inductive voltage parameter of the PM
motor.
Obtain the datasheet of your PM motor from the motor manufacturer and set the inductive
voltage parameter (for one phase).
This value must be set in "Vp/(rad/s)." If the datasheet provides this parameter in a different
unit, you need to perform unit conversion.
Example
If, for a 4-pole PM motor, the inductive voltage parameter for one phase is 10 [mV/r/min],
the set value can be calculated as follows:
10 [mV/r/min] = (10/1000 [V]) × (√2) × (60 [s]) / ((2π × 4 [pole] / 2) [rad]) = 0.0675
[Vp/(rad/s)]
(5) In the PM Motor Parameter J (H110), set the moment of inertia of your PM motor.
Calculate the motor-shaft conversion of the moment of load inertia, add the moment of iner-
tia of the motor to it, and set the sum.
(6) Set the DC Injection Braking Selection (A051) to 00 (Disabled) (default).
If the DC Injection Braking Selection (A051) is set to 01 (Enabled), change it to 00 (Dis-
abled).
If these parameters are set to Enabled, auto-tuning will not be completed.
(7) Set the motor cable length in the Motor Cable Length (b033).
Set the Motor Cable Length (b033) according to the length of your motor cable.
Parameter
No.
H103
H104
A003
A004
A082
H105
b012
6 - 58
Rated frequency
=
Function name
0.1/0.2/0.4/0.55/0.75/1.1/1.5/2.2/3.0/3.7/4.0/
PM Motor Capacity
5.5/7.5/11.0/15.0/18.5
PM Motor Pole
2/4/6/8
Number
10 to 48: Do not set.
1st Base Frequency
30.0 to 1st Maximum Frequency (A004)
1st Maximum Fre-
1st Base Frequency (A003) to 400.0
quency
200-V class: 200/215/220/230/240
1st Motor Rated
Voltage Selection
400-V class: 380/400/415/440/460/480
PM Motor Rated
0.20 × Rated current to 1.00 × Rated current
Current
1st Electronic Ther-
0.20 × Rated current to 1.00 × Rated current
mal Level
Rated rotation speed (Maximum rotation speed) [min
Number of poles [pole]
Data
Multi-function Compact Inverter 3G3MX2-V1 User's Manual (I585-E1)
-1
] ×
120
Default data
Unit
Maximum
applicable
motor
capacity
Dependent
pole
on capacity
60.0
60.0
200 or 400
Rated
current
Rated
current
kW
Hz
Hz
V
A
A