Figure 3-5 Ac Connections From Gt Inverter To Utility Service Panel - Xantrex GT2.5-NA Owner's Manual

Grid tie solar inverter
Table of Contents

Advertisement

Wiring the Inverter
3–8
http://www.wholesalesolar.com/inverters.html
To wire the main utility service panel to the GT Inverter:
1. Install conduit from the main utility service panel to the wiring/disconnect
box of the GT Inverter. Run the two HOT wires (L1 and L2) and ground wire
from the service panel through the conduit and into the inverter wiring box.
2. Install or use an existing double-pole 20-Amp circuit breaker (or two
single-pole breakers, ganged) in the main utility service panel, and ensure that
the breakers are set to OFF.
3. Connect the ground wire (green or bare copper) from the ground bar in the
main utility service panel to the GND bar in the wiring box.
4. Connect the L1 HOT wire (black) from the double-pole breaker installed in
the main utility service panel, to the L1 GRID terminal in the wiring box.
5. Connect the L2 HOT wire (red) from the double-pole breaker installed in the
main utility service panel, to the L2 GRID terminal in the wiring box.
6. Ensure all connections are correctly wired and properly torqued according to
values shown in Table 3-1 on page 3–5.
Xantrex GT Inverter
Wiring Box
GND bar
AC/DC Disconnect Switch

Figure 3-5 AC Connections from GT Inverter to Utility Service Panel

http://www.wholesalesolar.com/inverters.html
Utility Grid
L1 L2
Neutral
Utility
Meter
L1 L2
Neutral
Main Utility
Service Panel
L1
L2
NEUTRAL
L1
L2
Neutral
Ground
GROUND
G
Primary Earth
Ground
975-0245-01-01
-to-
Bond