Installation
Rectangular slots × 25:
0.8 × 3 (5/16 × 1
)
3/16
Mounting flanges
Figure 2-8 Mounting Bracket and GT Inverter
Clearance Requirements
2–18
http://www.wholesalesolar.com/inverters.html
Mounting bracket
25.3 (10)
Mounting slots for securing the inverter
For optimal and safe operation, ensure there is adequate clearance around the
inverter. The minimum clearance recommendations in Table 2-2 assume a vertical
mounting. If clearances are reduced below these minimums, rated power may not
be achieved.
Table 2-2 Inverter Clearance Requirements
Location
Minimum Clearance
Above
30 cm (12 inches)
Below:
Outdoors:
•
Inverter
•
100 cm (39 inches)
•
Bracket
•
110 cm (43 inches)
Indoors: the same clearances are
recommended but not required.
In front
Sufficient room to allow for easy access to read the display and to prevent
accidental contact with hot surface.
On sides
Units can be mounted side by side with no clearance between them, but 15
cm (6 inches) of clearance around the outermost two units is recommended.
In hot climates, some clearance between units may be needed to prevent
thermal derating.
http://www.wholesalesolar.com/inverters.html
Back side of the inverter
The inverter extends below the
bracket by approximately 10 cm
(4 inches)
Mounting flanges
All measurements
in cm (inches).