Table 3-1 Torque Values For Wires - Xantrex GT2.5-NA Owner's Manual

Grid tie solar inverter
Table of Contents

Advertisement

975-0245-01-01
http://www.wholesalesolar.com/inverters.html
The following procedure is illustrated in Figure 3-4. If there is more than one PV
string, label the positive and negative wire pairs appropriately (for example:
PV1-String #1 POS, PV1-String #1 NEG, PV1-String #1 GND,
PV1-String #2 POS, etc.).
To wire the PV array to GT Inverter:
1. Remove the wiring/disconnect box cover (see page 3–2).
2. Install DC conduit from the PV string(s) to the GT Inverter wiring box,
through one of the knockout holes.
3. Route the wires from the PV string(s) through the conduit and into the wiring
box.
4. Connect the DC Ground from each PV string to the GROUND bar in the
wiring box.
5. Connect the POSITIVE (+) wire from the PV1 string #1 to one of the PV+
terminals in the wiring box. Double check that the wire is in the proper
location and tighten the screw.
6. Connect the NEGATIVE (–) wire from the PV1 string #1 to one of the
PV– terminals. Double check that the wire is in the proper location and
tighten the screw.
7. Repeat for the PV1 string #2, if there is one.
a) Connect the POSITIVE (+) wire from the PV1 string #2 to the unused
PV+ terminal.
b) Connect the NEGATIVE (–) wire from the PV1 string #2 to the unused
PV– terminal.
Double check that the wires are in the proper locations and tighten the screws.
8. If required, connect the DC ground electrode conductor tot he DC or AC
ground electrode as per NEC 690.47.
9. Ensure all connections are correctly wired and properly torqued according to
values shown in Table 3-1.

Table 3-1 Torque Values for Wires*

Wire Size
AWG
14 to 10
2.5 to 6.0
8
10.0
6
16.0
*Use copper conductors only.
http://www.wholesalesolar.com/inverters.html
2
mm
in-lb.
35
40
45
Connecting the DC Wiring
Torque
Nm
4.0
4.5
5.1
3–5

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gt3.0-naGt3.3-na

Table of Contents