Sensor Based Thermal Specification Design Guidance
8.4.3
DTS 1.1 A New Fan Speed Control Algorithm without
T
AMBIENT
In most system designs incorporating processor ambient inlet data in fan speed control
adds design and validation complexity with a possible BOM cost impact to the system.
A new fan speed control methodology is introduced to improve system acoustics
without needing the processor inlet ambient information.
The DTS 1.1 implementation consists of two parts, a
a
point at DTS = -1.
CA
The
CA
worst case system design Tambient design point:
For example, for a 95 TDP part, the Tcase max is 72.6C and at a worst case design
point of 40C local ambient this will result in
Similarly for a system with a design target of 45 C ambient the
will be 0.29 C/W.
The second point defines the thermal solution performance (
Table 8-1
These two points define the operational limits for the processor for DTS 1.1
implementation. At T
is better than or equivalent to the required
CA
speed should be set at DTS = -1 such that the thermal solution performance is better
than or equivalent to the
temperature, the fan speed controller must linearly change the fan speed from DTS =
T
CONTROL
DTS 1.1.
Thermal/Mechanical Specifications and Design Guidelines
Data
point at DTS = -1 defines the minimum
= (T
CA
= (72.6 - 40) / 95 = 0.34 C/W
CA
lists the required
CA
the fan speed must be programed such that the resulting
CONTROL
requirements at Tambient_Max. Based on the processor
CA
to DTS = -1 between these points.
CA
required at TDP considering the
CA
- T
) / TDP
CASE_max
Ambient target
for various TDP processors.
listed in
CA
Figure 8-8
requirement at T
CONTROL
at DTS = -1
CA
) at T
.
CA
CONTROL
Table
8-1. Similarly the fan
gives a visual description on
and
needed
73