P o o l C o p E v o l u t i o n M a n u a l : E V 4 4 M A N U S
Bottom Force
This setting is displayed for Skimmers pools with suction valve only.
Define how long the water circulation is forced via the bottom drain after a backwash.
This setting is important with slim skimmers to avoid loss of pump priming, allowing
the pool to refill before turning the suction from skimmers.
Draining
This setting is displayed if mode: REDUCE, AUTO.
Set the duration for the water reduction cycle.
If the level is detected above setpoint, then PoolCop will reduce water level following
this logic:
With skimmers pools, reduction will be launched if level sustains above
setpoint for 15 minutes.
With rimflow pools, pump will be started immediately when level is detected
above level and will run until either:
level returns
o
Level stays above setpoint for 15 minutes, which will launch a water
o
level reduce cycle.
Level stays at setpoint for 3 hours, which will also launch a water level
o
reduce cycle.
Up to three cycles will be carried out per day.
Priming
Ensure Solenoid valve is correctly connected and powered.
Commanding priming ON will activate the SOV for 60 seconds allowing the water to
flow. Priming is stopped when quitting the menu or after 60 seconds.
P a g e | 8 4
NORMAL.
Text:
Bottom Force
Default:
10min
Entries:
10 to 120min
Text:
Draining
Default:
120 seconds
Entries:
10–600 seconds
Text:
Priming
Default:
OFF
Entries:
ON;
OFF