Page 1
Installer and User Manual Date: October 09 , 2024 Manual Version: GN44MANUS Firmware Version: V44 Product Versions: PoolCop Genesis NSF/ANSI/CAN 50...
Page 2
P o o l C o p G e n e s i s M a n u a l : G N 4 4 M A N U S Change Summary August 24 , 2020 Original Issue, Certification NSF/ANSI/CAN Standard 50. January 22 , 2021 Update FAC, Decals.
PoolCopilot Functions ..........................................120 Troubleshooting ............................................121 Section 7 Spare Parts and Diagrams ....................... 122 GN3100 Data Control Connection Unit DCCU Genesis ............................122 SO491x pH+ORP SE Sensor Kit ......................................123 GN4224 Kit Sensor pressure 4m cable ................................... 124 GN4211 Kit Water Temperature Sensor 4m Cable ..............................124 Decal and Markings Location Diagrams ..................................
Page 4
P o o l C o p G e n e s i s M a n u a l : G N 4 4 M A N U S Flow Switch ..............................................129 pH+ORP Sensors............................................130 Free Available Chlorine Sensor ......................................130 Water Level Control ..........................................
Page 5
P o o l C o p G e n e s i s M a n u a l : G N 4 4 M A N U S Figures Figure 1 - Serial Number Location ............................................11 Figure 2 - DCCU ..................................................... 18 Figure 3 - Air Temperature Sensor ............................................
P o o l C o p G e n e s i s M a n u a l : G N 4 4 M A N U S NTRODUCTION Section 1 Foreword ................................................6 Notes, Cautions, Warnings and Definitions ..................................6 Important Information, Safety Notices and Precautions ..............................
Instructions given below are all important for your safety. PoolCop is a product of superior design, engineering and manufacture and should be treated with care. The information contained in this section will help you fulfil the warranty obligations and make use of this product for many years.
Page 8
P o o l C o p G e n e s i s M a n u a l : G N 4 4 M A N U S WARNING: Equipment should not be installed near flammable gas or products. In the event of the escape of gas or dangerous products, there is risk of fire and explosion.
P o o l C o p G e n e s i s M a n u a l : G N 4 4 M A N U S WARNING: Any person using, adjusting, or monitoring the equipment must be at least 18 years of age and be familiar with these instructions and the contents of this manual.
P o o l C o p G e n e s i s M a n u a l : G N 4 4 M A N U S ARRANTY ECORDS Section 2 PoolCop Genesis Warranty ........................................12 Routine Maintenance ..........................................13 Routine Pool Maintenance ....................................... 13 PoolCop Maintenance ........................................ 13 Pool Winterization ........................................
In the context of this warranty, the PCFR’s sole obligation is to repair or replace products which meet the conditions of this warranty. PoolCop is not responsible for any loss or damage relating to products, to service, to this warranty or any other, including: Loss of use of the pool.
WARNING: Chemical consumables are hazardous substances and must be handle with extreme care and caution. PoolCop Genesis Annual Service The equipment requires an annual service by a qualified technician. Refer to the equipment Maintenance Card (2.3.2.4) for details and dates due. Essential service items are: Check water balance.
Page 14
P o o l C o p G e n e s i s M a n u a l : G N 4 4 M A N U S PoolCop Genesis Site Visit Checklist The following checklist will maintain equipment in good condition and optimize service calls.
Check pH Sensor Calibration Check Leaks Annual Service Check pH Sensor Calibration Check Leaks Annual Service Check pH Sensor Calibration Check Leaks PoolCop Genesis is guaranteed for 2 years provided that warranty conditions are met. P a g e | 1 5...
Page 16
When re-opening the pool after passive winterization (or out or service for a period of time) carry out the following procedure: Replace the pH+ORP sensor if removed. Perform an annual service (as per 2.3.2.2 PoolCop Genesis Annual Service). Continue with the normal maintenance cycles of the pool and the equipment.
Drum Level Sensors for detection of drums requiring replenishment. XM8 Extension Module adds an extra 8 inputs and 8 relays outputs. PoolCop Chlorine Sensor FAC for reporting and alerting of Free Available Chlorine in ppm (DPD1). P a g e | 1 8...
Page 19
P o o l C o p G e n e s i s M a n u a l : G N 4 4 M A N U S Before commencing installation, the technician should confirm the following with the pool owner: Preferred location of DCCU.
P o o l C o p G e n e s i s M a n u a l : G N 4 4 M A N U S 3.3 I DCCU NSTALLING THE M o u n t i n g t he D C C U CAUTION: Use only existing predrilled holes for mounting the DCCU.
P o o l C o p G e n e s i s M a n u a l : G N 4 4 M A N U S C a b l e s S e le c t i o n a n d C o n n e ct i o n For pump and auxiliary control: SPT-1 or SPT1-W, 2 cores, AWG18.
Page 22
P o o l C o p G e n e s i s M a n u a l : G N 4 4 M A N U S See the appropriate section of this manual for connection details. Feed auxiliary equipment control cables through appropriate compression gland into the DCCU.
P o o l C o p G e n e s i s M a n u a l : G N 4 4 M A N U S C o n n e ct i n g a S i n g le S p ee d P u m p Disconnect the power supply to and from the existing pump timer.
C o n n e ct i n g a V a r ia b l e S p ee d P u m p See the VARIABLE SPEED PUMPS GUIDE downloadable on our internet website www.poolcop.com in RESOURCES /DOWNLOADS section for compatibility, connection, control and programming.
P o o l C o p G e n e s i s M a n u a l : G N 4 4 M A N U S Pentair IntelliFlo3 VSF Figure 10 - Pentair IntelliFlo3 VSF Pentair SuperFlo VS/VS2 PN356324Z PN353129Z Speed...
P o o l C o p G e n e s i s M a n u a l : G N 4 4 M A N U S Zodiac FloPro VS Figure 14 - Zodiac FloPro VS Binary Combination This is option is not related to a specific pump but can be used to control several mono speed pumps.
P o o l C o p G e n e s i s M a n u a l : G N 4 4 M A N U S 3.4 I NSTALLING TANDARD EATURES P u m p P r e s s u r e a n d W a t er T e m p er a tu r e S en s or s The Pump Pressure Sensor must be installed to monitor pump priming, inform about filter clogging and prevent chemicals to be injected when there is no pressure.
P o o l C o p G e n e s i s M a n u a l : G N 4 4 M A N U S Installation with Flow Cell Cap accessory (GN4202.04) Flow direction Flow direction FLOW Figure 19 - Figure 20 -...
P o o l C o p G e n e s i s M a n u a l : G N 4 4 M A N U S A i r T e mp er a tu r e S en s or The optional Air Temperature Sensor measures outside air temperature, displays this on the screen, and is used for antifreeze protection if configured in the POOL DATA...
P o o l C o p G e n e s i s M a n u a l : G N 4 4 M A N U S C i r c u l a t i o n F l o w De t e c t i on S e n s o r A water circulation sensor may be installed to prevent chemicals to be injected when there is no flow at the injection points, where required.
P o o l C o p G e n e s i s M a n u a l : G N 4 4 M A N U S There must be a 5 mm (0.2”) minimum gap between end of the paddle and opposite pipe wall (see Figure 28 - Flow Switch Paddle Length Adjustment).
With Extension Module and Pool cover function installed, Aux14 is dedicated to open cover, Aux15 to close. With Extension Module and Jetstream function installed, Aux13 is dedicated to Jetstream pump control. Each auxiliary relay has its own dedicated timer, programmed in the PoolCop AUXILIARIES MENU.
P o o l C o p G e n e s i s M a n u a l : G N 4 4 M A N U S Relay Timer Programming Each auxiliary relay can be programmed with one daily timer cycle. Auxiliary relays can be slaved to run only if filtration is running.
Pool Cover Detection An external pool cover sensor can be connected to an Input to inform PoolCop that the cover is in the closed position. Programming in the Pool Data menu then allows for adjustment of filtration duration and water treatments.
P o o l C o p G e n e s i s M a n u a l : G N 4 4 M A N U S 3.5 I NSTALLING ATER REATMENT G e n er a l The equipment is compatible with all water treatments.
P o o l C o p G e n e s i s M a n u a l : G N 4 4 M A N U S Installation on threaded pipe Figure 44 - Sensors on Threaded 3” Pipe Sensor Housing must be placed in a M24x1.5 threaded hole in a minimum 3”...
P o o l C o p G e n e s i s M a n u a l : G N 4 4 M A N U S Figure 47 - SO4912 Spacing, Grab Ring Adjustment Figure 48 - SO4913 Spacing, Grab Ring Adjustment Check/adjust compression ring and O-Ring accordingly.
P o o l C o p G e n e s i s M a n u a l : G N 4 4 M A N U S p H C o n tr o l WEAR HAND PROTECTION: Always wear correct chemical resistant hand protection when handling chemicals.
P o o l C o p G e n e s i s M a n u a l : G N 4 4 M A N U S Installing the Feeder Pump Install the feeder pump, associated suction and injection pipes and connectors as per the feeder pump installation manual. Ensure that the correct liquid consumable pH- or pH+ is installed and secured.
P o o l C o p G e n e s i s M a n u a l : G N 4 4 M A N U S D i s in f e c t i on WEAR HAND PROTECTION: Always wear correct chemical resistant hand protection when handling chemicals.
P o o l C o p G e n e s i s M a n u a l : G N 4 4 M A N U S Dosage controlled by volume and temperature This function adjusts disinfectant volume injected based on: Dosing pump flow rate.
P o o l C o p G e n e s i s M a n u a l : G N 4 4 M A N U S Salt Water Chlorination A correctly specified salt water chlorination system and installation kit is required. When salt water chlorination is used for treatment, regular water analysis will be carried out to ensure that salt consumables and free chlorine levels remain within the required limits.
P o o l C o p G e n e s i s M a n u a l : G N 4 4 M A N U S 3.6 I NSTALLING PTIONS Various equipment options are available. These serve to increase autonomy and enhance functionality. W a t er L e ve l C o n tr o l Automatic water level control functionality is integrated.
P o o l C o p G e n e s i s M a n u a l : G N 4 4 M A N U S Installing the Water Line Version, with 4 Terminals Secure the water level sensor (using stainless steel self-tapping screws, or appropriate adhesive) at the correct height on the inside of the skimmer or on the waterline.
Connect the 2-core wire from the valve solenoid to the connector on J20 marked (VALVE 24VAC) according to Figure 55 - Connecting Water Level. Polarity is not important. Reconnect electrical power supply to the PoolCop DCCU. Switch the DCCU ON.
P o o l C o p G e n e s i s M a n u a l : G N 4 4 M A N U S I n s ta l l in g X M 8 E xte n s i o n M o du l e Read before starting electrical connection.
P o o l C o p G e n e s i s M a n u a l : G N 4 4 M A N U S for more details). XM8 box is provided with compression glands size PG7 (for external diameter 3.5mm to 8mm), PG9 (for external diameter 3.5mm to 8mm) and PG11 (for external diameter 4mm to 10mm).
Page 49
P o o l C o p G e n e s i s M a n u a l : G N 4 4 M A N U S Outputs (relays) table: Relay Relay Function Connector Rating Examples of possible use Label AUX8 6A/24V...
P o o l C o p G e n e s i s M a n u a l : G N 4 4 M A N U S C o n n e ct i n g E qu i p me n t Connecting a Pool Cover A pool cover control functionality is available in Equipment settings.
P o o l C o p G e n e s i s M a n u a l : G N 4 4 M A N U S Connecting a Jetstream Pump A Jetstream pump is usually operated with a pneumatic push button in the pool. If the push button is connected to the XM8 Extension Module, Jetstream will also be operable remotely and user will be able to choose a running duration (see Erreur ! Source du renvoi introuvable.
If this equipment stays on for longer than 2 seconds, IMMEDIATELY switch OFF the DCCU. Recheck all connections. If only the pump runs, disconnect the circuit breaker, switch ON the PoolCop and reset factory default settings. Now reconnect the pump circuit breaker and continue with commissioning.
Explain that once the water is balanced, the PoolCop takes over the filtration and other functions as installed within normal parameters. Remind the owner that the PoolCop is a management system, not a repair system. Events outside of the norm may require intervention and water balance.
The pool will be a healthier swimming environment. PoolCop is not a repair system. Pay prompt attention to any Alerts. In the unlikely event of malfunctions call a qualified technician. Following the guidelines in this manual and maintain the equipment in accordance with the maintenance schedule to ensure trouble free operation and an easily maintained swimming pool.
P o o l C o p G e n e s i s M a n u a l : G N 4 4 M A N U S Figure 61 - DCCU Display and Keypad 4.3 M ENUS Manual Control Filtration Modes Auxiliaries...
P o o l C o p G e n e s i s M a n u a l : G N 4 4 M A N U S M a n u a l C o n t r o l Switch Pump Manually switch the pump ON or OFF at any time (if no freeze conditions).
Program filtration timers and duration, manually or in automatic modes. Whenever quitting the FILTRATION MODES menu, PoolCop checks and adjust the status of the pump and auxiliaries and switches them ON or OFF as required to match programmed run times. Cycle1 =00:00-00:00 Filtration is stopped.
Whenever quitting the AUXILIARIES menu, PoolCop checks and adjust the status of the pump and auxiliaries and switches them ON or OFF as required to match programmed run times. AUX channels operate in the same manner, but some channels may be required for specific functions.
Pressure inhibit Measure pH Measure pH Calibrate pH Calibrate pH Read FAC (if PoolCop Chlorine Sensor FAC is installed) Value FAC Calibrate FAC Calibrate FAC (if PoolCop Chlorine Sensor FAC is installed) Calibrate conductivity (If PoolCop Ocean and sensor Calibrate Conductivity...
P o o l C o p G e n e s i s M a n u a l : G N 4 4 M A N U S P o o l C o p C l o u d Connected PoolCop is connected to, the cloud Registered PoolCop is associated to a pool...
Water temperature and air temperature are shown alternatively on the same row. An Up or Down steady arrow may appear on the right of pH value: this will be the case if: pH is controlled by PoolCop (pH control is installed, and pH type is pH+ or pH-). •...
Start the Pump Normally, the filtration pump is controlled automatically by PoolCop using filtration in manual timer or automatic modes. If, however you want to run the pump at another time or need to restart the pump after stopping it for any reason, this is done from MANUAL CONTROL.
Change the Pump Speed This feature is available with variable speed pumps only; for configuration see the PoolCop Variable Speed Pump Guide. Pump speed is linked to filtration and Filter Cleaning Cycles; the speed can be changed by the user with the pump ON and this speed will be maintained until the next programmed Filtration Timer cycle commences or until the next filter cleaning cycle starts.
Page 65
14.2 Water Temp 82.4 °F On the PoolCop main display, next to Pump you will see the Level Normal mode in which the pump and filtration are running, or OFF. The mode that has started and/or is now causing the pump to 760mV be on will be displayed.
Page 66
TIMER mode, filtration durations are not managed by PoolCop but chosen by the end user who must then make sure to correctly set the duration according to pool needs. A too long duration will waste energy and a too short one may not allow to keep the pool in good conditions.
Page 67
This mode does not affect Cycle 2 settings. FORCED mode, the maximum daily duration is limited to 23:00; with either one or two stopped periods to allow for PoolCop measurement functions and daily self-test to occur. Normal automatic filter cleaning may occur during FORCED mode.
Page 68
(Cycle 1 and Cycle 2) for best results. It is recommended to leave a gap of at least 30 minutes between two timer cycles to allow PoolCop to take necessary measurements make subsequent adjustments and carry out the periodic backwash if selected.
Page 69
PoolCop has two means of detecting a freezing risk. It is recommended that BOTH freezing protections be utilized, and that freezing protection be selected ON in the POOL DATA menu throughout the year.
Setting any timer to 00:00-00:00 (or any combination with same start and stop times) deactivates that timer. Whenever quitting the AUXILIARIES menu, PoolCop checks and adjust the status of the auxiliaries and switches them ON or OFF as required to match programmed running times. Switch Auxiliaries ON/OFF...
P o o l C o p G e n e s i s M a n u a l : G N 4 4 M A N U S E q u i p me n t C o n t r o l ( r e qu i r e s X M8 E x ten s i on M o d u le ) Equipment are specific devices such as Pool Cover, Jetstream.
P o o l C o p G e n e s i s M a n u a l : G N 4 4 M A N U S S er v i c e M o de In service mode, PoolCop stops all automatic actions. 1 2 : 4 6 : 0 1...
A l e r t s a n d S y s t e m M e s s a g es An Alert or a System Message is the way PoolCop notifies you of something out of the ordinary.
Page 75
Alerts list and troubleshooting NOTE: The alerts list, the alert triggers and the troubleshooting corrective guidelines are detailed in the TROUBLESHOOTING MANUAL downloadable on www.poolcop.com in resources/downloads. View and Reset Alerts 1 2 : 4 6 : 0 1 0 1 / 0 6 / 2 0 2 0 Pump AUTO : 14.2...
P o o l C o p G e n e s i s M a n u a l : G N 4 4 M A N U S 5.1 P RIOR TO OMMENCING ROGRAMMING C l e a n t he F i l t er Ensure that the filter media is properly maintained and cleaned as per the manufacturer’s instructions and code requirements.
Set Cycle 1 as desired. Duration will be taken into account when FORCE72H; calculating Cycle 2 duration. 24/24; Set the Cycle 2 Filtration ON time. PoolCop calculates and sets the OFF NO PUMP time, with X indicated. The duration is automatically calculated based on the average measured temperatures during filtration in the last 24-hour period.
Cycle 2 will default to 8 hours. Once the filtration has run for approximately 10 minutes an accurate measurement of pool water temperature will enable your PoolCop to update the filtration duration. C y c l e 1 T i m es Filtration timer Cycle 1 is used to set fixed duration filtration times.
Operation Modes of auxiliaries are related to auxiliary names. : 02:30 Auxiliary timers have one cycle in any 24-hour period. : 06:45 When quitting the AUXILIARIES menu, PoolCop checks the status of Slave : NO the auxiliaries, and switches them as required to match Weekday ✓✓✓✓...
P o o l C o p G e n e s i s M a n u a l : G N 4 4 M A N U S “ A u x ” M o de Manual mode allows manual ON/OFF commands only. No automatic function will Text: Mode apply.
Entries: YES; Water Level Control Modes With mode: READ, PoolCop will indicate the water level on the screen but will not Text: Mode take any action to control it. Should the level be...
Page 84
P o o l C o p G e n e s i s M a n u a l : G N 4 4 M A N U S Setpoint Define the targeted level during refill. Text: Setpoint Normal: the second slot of the sensor is targeted. Default: High •...
Draining Set the duration for the water reduction cycle; Default: 120 seconds If the level is detected above setpoint, then PoolCop will reduce water level following Entries: 10–600 seconds this logic: With skimmers pools, reduction will be launched if level sustains above setpoint for 15 minutes.
Page 86
Installed Text: Installed INSTALLED: YES PoolCop will control the pH according to set point value. pH Default: Control display will be activated; pH Control Alerts will be activated. Entries: YES; If set to NO, these functions are deactivated.
Page 87
Setpoint at Current Temperature Text: SetPoint xx °C PoolCop can automatically adjust the actual pH Setpoint as a function of temperature (SetPoint xx °F) to ensure year-round optimal water treatment. This adjusted Setpoint is displayed against current water temperature if TEMP ADJUST is set to YES.
Q U I T Installed Text: Installed INSTALLED: YES, PoolCop will control the ORP according to set point value. Default: ORP Control display will be activated; ORP Control Alerts will be activated. Entries: YES; If set to NO, these functions are deactivated.
Commanding priming ON will activate Aux6 for 60 seconds allowing the feeder pump Entries: to prime. Priming is stopped when quitting the menu or after 60 seconds. Diag Ocean (if PoolCop Ocean, Space or DA-GEN Connected) See PoolCop Ocean Guide. P a g e | 8 9...
10PM and re-calculated each day at midnight. S E L E C T Q U I T Installed Text: Installed INSTALLED: YES, PoolCop will control the Remnant injection according to Default: parameters settings. Entries: YES; If set to NO, this function is deactivated. Aux Channel...
Priming is stopped when quitting the menu or after 60 seconds. F r ee A v a i la b l e C L This menu is detailed in PoolCop Chlorine Sensor FAC Installer and User Manual. P a g e | 9 1...
S E L E C T Q U I T S er v i c e M o de In service mode, PoolCop stops all its automatic actions. Every connected device Text: Service Mode (pump, Auxiliaries, water refill…) is stopped when using this mode.
Ensure that alkalinity is correct, and the body of water is adequately mixed, before calibration. NOTE: During the calibration process, PoolCop compares the "offset" of the probe to the signal that would be delivered by a perfect probe. This offset is essentially related to sensor aging.
Setting the temperature to 0°C (32°F), deactivates protection. A d j u s t Wa t er T e m pe r a t u r e Allows you to align PoolCop temperature indication to third party equipment like a Text: Temp heat pump by adding an offset to the temperature indication.
YES, NO CAUTION: PoolCop freezing protections can only assist in the protection of equipment. PoolCop cannot guarantee that damage will be avoided under all circumstances, as this depends on many factors. No responsibility will be accepted for damage caused due to freezing.
Page 96
Filtration Reduction When Pool Cover is Detected Closed To be effective, this functionality assumes the connection of pool cover, or mobile floor limit switch to a PoolCop input. (see 5.6.4 Inputs). Depending if pool is configured with a single or multi-speed pump, reduction strategy is different:...
HAYWARD Range VSTD; UP arrow and press SELECT; now use the arrows to select the pump make and BADU Eco Touch-pro; model installed. Refer to the PoolCop Variable Speed Pump Guide for further BADU 90 Eco Motion; details including connecting and programming.
Page 98
Round UP = 0.20 bar (2.3 PSI) Add 0.20 bar (2.9 PSI) = 0.40 bar (5.8 PSI) Activate Pump Protection PoolCop protects the pump, by switching OFF the pump and integrated water Text: Prot. Pump treatments in the event pressure measured is below the Prot. Pressure for 8 minutes.
Let filtration run for a few minutes to expel any air in the system. (-10.0 to 14.5 PSI) Note the base pressure reading on the PoolCop. Round off to next higher round number and add a 0.10 bar (1.5 PSI) margin.
Page 100
P o o l C o p G e n e s i s M a n u a l : G N 4 4 M A N U S On speed Text: On speed Only when a FlowVis flowmeter is configured (see above) and the pump is multispeed type.
Page 101
P o o l C o p G e n e s i s M a n u a l : G N 4 4 M A N U S Pump run Displayed if CLEAN : AUTO CLEAN : MANUAL. Text: Pump run Select if the pump must be stopped (Pump Run = NO) or not, to change cleaning valve...
Page 102
P o o l C o p G e n e s i s M a n u a l : G N 4 4 M A N U S Suction valve A BESGO 3-way valve can be added to pump suction line to get water either from the Text: Suction surface (skimmer or buffer tank) or from the bottom of the pool.
Consumables; Consumables; Pool Cover; Salt System; Filtration Start; Filtration Stop; Various inputs can be installed and configured for use with PoolCop. JetStream; Note: if Filtration Mode is set to PUMP, Filtration Start and Filtration Stop Flow Switch; functions are not available.
Page 104
P o o l C o p G e n e s i s M a n u a l : G N 4 4 M A N U S Sense of Action The sensor action configures whether the alert action is taken when the circuit is closed (direct action) or open (reverse action). For example: If the thermostat contact closed indicates a freezing risk, choose “When Closed”.
Page 105
Generates an alarm in the non-closed position. If the pool is equipped with a variable speed pump, PoolCop switches on the configured speed. When the cover is re-opened during a cycle of operation of the pump, the speed associated with this cycle is restored.
P o o l C o p G e n e s i s M a n u a l : G N 4 4 M A N U S Consumables 5 seconds The connection of a consumables low level detector (typically a float switch on a suction wand) triggers an alert when low level is detected.
The remote control of the Pool Cover is reserved for maintenance operations carried out by an authorized installer. Installed Text: Installed INSTALLED: YES, PoolCop will be able to control the Pool Cover opening and Default: closing. Entries: YES; If set to NO, the Pool Cover (if any) will be operated manually.
Page 109
P o o l C o p G e n e s i s M a n u a l : G N 4 4 M A N U S Close Setting (Aux15 Settings) A U X 1 5 : R s r v ' d C o v e r >...
Page 110
Q U I T NOTE: If the pool has a cover and the cover is detected closed by PoolCop, then the JetStream pump is forced OFF for safety reasons. JetStream pump is only allowed to run when the cover is not closed.
S E L E C T Q U I T Setting Time Set and adjust system Time. Text: Time PoolCop adjusts for daylight saving if connected to the PoolCopilot server. Entries: Setting Date Set and adjust system Date. Text: Date PoolCop adjusts for daylight saving if connected to the PoolCopilot server.
IT ; TK ; DE ; SP ; Units Menu Text: Units Select PoolCop display units Default: SI * * Default is SI for EU version of firmware, set to US for US versions. Entries: SI ; Factory Reset Text:...
Values: YES; introuvable. Erreur ! Source du renvoi introuvable.. R e g i s t er e d Once PoolCop has been associated with a pool, it will be seen as registered. Text: Registered If not registered, status is NO.
PoolCopilot Functions ..........................................120 Troubleshooting ............................................121 Error Messages ........................................... 121 PoolCop will not connect to the server ................................121 No data displayed ........................................121 No graphs displayed in “History” ..................................121 P a g e | 1 1 6...
C h e c k t h e N e t w o r k C o n n e c t i on On PoolCop screen, go to Menu/Configuration/Factory Settings/network and note the MAC address as shown below: N E T W O R K...
Tick the boxes to agree to terms of use, and • optionally “I agree to received data from PoolCop” to receive newsletters. Click on “Submit” to register and create your • new account.
Complete the form: The Mac Address is the unique identification of • the new PoolCop. This code is written on the sticker located on the PoolCopilot Web RJ45 module inside the ABS Box. The nickname allows easy identification of the •...
6.4 P OPILOT UNCTIONS All PoolCop functions are possible from PoolCopilot. Additional functions are constantly made available as PoolCopilot evolves. These functions are made available via the web interface for all users. The list includes: Unlimited email alerts and notifications...
If access is not available, check with router provider / IT service. Check IP address on Network menu. If IP is 0.0.0.0, no IP address has been affected to PoolCop, check if the DHCP mechanism is enable on the router and if there is no restriction to access Internet (restrictions on MAC addresses for example) Check SVR address on Network menu.
RJ45 Cable 1m CF1140.02 Panel Mount Socket RJ45 IP68 CF1140.04 Cap RJ45 IP68 CF1114 Switch CCU GN3201.01 Face Plate Decal and Keypad Genesis SN007 Decal Serial Number CCU Genesis GN3102.01 Datalink Cable Short (not shown) CF1218.01 PCB Connection SE Data PCB005-C CF1220.01 PCB Micro with LCD Screen PCB004-C GN3105.02...
P o o l C o p G e n e s i s M a n u a l : G N 4 4 M A N U S 7.3 GN4224 K ENSOR PRESSURE M CABLE PART JT0004 O-Ring Plug VDU GN4224.03 Sensor Pressure 4m Cable AC6800.06...
P o o l C o p G e n e s i s M a n u a l : G N 4 4 M A N U S 7.5 D ECAL AND ARKINGS OCATION IAGRAMS D C C U D e ca ls a n d Ma r k i n g s See 7.5.1.1 See 7.5.1.6.1 See 7.5.1.6.5...
The unit complies with all applicable essential requirements of the Directives. Manufacturer: PCFR SAS, La Remise, 130 boulevard du Nord, 84160 Cucuron (FRANCE) Equipment: PoolCop Model name: PoolCop Genesis Directives Titles Harmonized Standards EN 61010-1:2010 2014/35/EU Low Voltage Directive...
The unit complies with all applicable essential requirements of the Directives. Manufacturer: PCFR SAS, La Remise, 130 boulevard du Nord, 84160 Cucuron (FRANCE) Equipment: PoolCop Model name: PoolCop Genesis Norms Titles Sections Conducted emissions : AC: 150kHz – 30MHz FCC §15.107 FCC part 15B Radiated emissions: 30 MHz –...
P o o l C o p G e n e s i s M a n u a l : G N 4 4 M A N U S Altitude 2000m Relative humidity 80% up to 31°C, linear decrease down to 50% at 45°C Wet Location The product has an enclosure that protected against splashing water, can be used in such wet location Current (Secondary)
Need help?
Do you have a question about the Genesis and is the answer not in the manual?
Questions and answers