Failure Diagnosis Instructions
Setting Monitoring Time
with the Teaching
Function
1,2,3...
Flags
1162
The following table shows the PLC Setup setting from the Programming Con-
sole.
Item
Programming Console
setting address
Name
Settings
Default setting
Times that PLC Setup set-
ting is read
Even if PLC Setup word 129 bit 15 is set to 1 (Do not record FAL Errors in
Error Log.), the following errors will be recorded:
• Fatal errors generated by FALS(007)
• Non-fatal errors from the system
• Fatal errors from the system
• Non-fatal errors from the system generated intentionally with FAL(006) or
FPD(269)
• Fatal errors from the system generated intentionally with FALS(007)
If a word address is specified for T, the monitoring time can be set automati-
cally with the teaching function. Use the following procedure when a word
address has been set for T.
1. Turn ON the FPD Teaching Bit (A59800).
2. FPD(269) will measure the time from the point when the execution condi-
tion for FPD(269) goes ON until the diagnostic output is turned ON.
3. If the measured time exceeds the monitoring time setting, a setting 1.5
times the measured time will be stored in T.
Name
Label
Error Flag
ER
Carry Flag
CY
The following table shows relevant words and flags in the Auxiliary Area.
Name
Address
FAL Error Flag
A40215
Executed FAL
A36001 to
Number Flags
A39115
Error Log Area
A100 to
A199
Setting
Word
129
Bit
15
FAL Error Log Registration
0: Record FAL Errors in Error Log.
1: Do not record FAL Errors in Error Log.
0: Record FAL Errors in Error Log.
Every cycle (when an FAL Error occurs)
Operation
ON if C is not within the specified range of 0000 to 01FF
or 8000 to 81FF.
ON if T is not within the specified range of 0000 to 270F.
OFF in all other cases.
ON if the diagnostic output is still OFF after the monitoring
time has elapsed.
OFF in all other cases.
Operation
ON when a non-fatal (FAL) error is registered in time
monitoring.
When a non-fatal (FAL) error is registered in time mon-
itoring, the corresponding flag will be turned ON. Flags
A36001 to A39115 correspond to FAL numbers 0001
to 01FF.
The Error Log Area contains the error codes and time/
date of occurrence for the most recent 20 errors,
including errors generated by FPD(269).