Data Control Instructions
Control
Item
data
Bit 01 of C+5 PID constant
change enable set-
ting
Bit 00 of C+5 PID forward/reverse
designation
Bits 13 to 14
ID starting integral
of C+6
manipulated vari-
able designation
(unit version 4.0 or
later only)
Bit 12 of C+6 Manipulated vari-
able output limit
control
Bits 08 to 11
Input range
of C+6
Bits 04 to 07
Integral and deriva-
of C+6
tive unit
Bits 00 to 03
Output range
of C+6
C+7
Manipulated vari-
able output lower
limit
C+8
Manipulated vari-
able output upper
limit
Contents
The timing of enabling changes
made to the proportional band
(P), integral constant (Tik), and
derivative constant (Tdk) for use
in PID calculations.
Determines the direction of the
proportional action.
Determines the initial integral
manipulated variable when PID
control is started (i.e., when the
input turns ON) .
Determines whether or not limit
control will apply to the manipu-
lated variable output.
The number of input data bits.
Determines the unit for express-
ing the integral and derivative
constants.
The number of output data bits.
(The number of output bits is
automatically the same as the
number of input bits.)
The lower limit for when the
manipulated variable output limit
is enabled.
The upper limit for when the
manipulated variable output limit
is enabled.
Setting range
0: At start of PID instruction exe-
cution
1: At start of PID instruction exe-
cution and each sampling period
0: Reverse action
1: Forward action
Bit 14 = 0 and bit 13=0:
Start from same integral manipu-
lated value as manipulated vari-
able output designation (Pre-Ver.
4.0 operation).
Bit 14 = 0 or 1 and bit 13 = 1:
Bumpless operation (i.e., start
from an integral manipulated
variable that will not abruptly
change the manipulated vari-
able output and result in a con-
tinuous change).
Bit 14 = 1 and bit 13 = 0:
Start with integral manipulated
variable = 0.
0: Disabled (no limit control)
1: Enabled (limit control)
0: 8 bits
5: 13 bits
1: 9 bits
6: 14 bits
2: 10 bits
7: 15 bits
3: 11 bits
8: 16 bits
4: 12 bits
1: Sampling period multiple
9: Time (unit: 100 ms)
0: 8 bits
5: 13 bits
1: 9 bits
6: 14 bits
2: 10 bits
7: 15 bits
3: 11 bits
8: 16 bits
4: 12 bits
0000 to FFFF (binary)
(See note 3.)
0000 to FFFF (binary)
(See note 3.)
Section 3-18
Change with
ON input
condition
Allowed
Not allowed
775