Text String Processing Instructions
Operand Specifications
Description
1248
Area
CIO Area
Work Area
Holding Bit Area
Auxiliary Bit Area
Timer Area
Counter Area
DM Area
EM Area without bank
EM Area with bank
Indirect DM/EM
addresses in binary
Indirect DM/EM
addresses in BCD
Constants
Data Registers
Index Registers
Indirect addressing
using Index Registers
Within the text string designated by S1, INS$(657) inserts the text string des-
ignated by S2, after the beginning word designated by S3, and outputs the
result to D as text string data (with NUL added at the end).
The maximum number of characters that can be inserted is 4,095 (0FFF hex).
If there are more than that, only 4,095 characters will be output to D (with NUL
added as the 4,096th character).
If either S1 or S2 is NUL, then the text string designated by the other one of
them will be output to D just as it is. If S1 and S2 are both NUL, then two NUL
characters (0000 hex) will be output to D.
Note INS$(657) can be processed in the background. Refer to the SYSMAC CS/
CJ/NSJ Series PLC Programming Manual (W394) for details.
S1
S2
CIO 0000 to CIO 6143
W000 to W511
H000 to H511
A000 to A447
A448 to A959
T0000 to T4095
C0000 to C4095
D00000 to D32767
E00000 to E32767
En_00000 to En_32767
(n = 0 to C)
@ D00000 to @ D32767
@ E00000 to @ E32767
@ En_00000 to @ En_32767
(n = 0 to C)
*D00000 to *D32767
*E00000 to *E32767
*En_00000 to *En_32767
(n = 0 to C)
---
---
---
,IR0 to ,IR15
–2048 to +2047 ,IR0 to –2048 to +2047 ,IR15
DR0 to DR15, IR0 to IR15
,IR0+(++) to ,IR15+(++)
,–(– –)IR0 to, –(– –)IR15
Section 3-33
S3
D
A448 to
A959
#0000 to
---
#0FFF
(binary) or
&0 to &4095
DR0 to DR15 ---
Inserted characters