3-32-7 HUNDRED-MS TIMER WAIT: TIMW(813) and TIMWX(816)

Purpose
Ladder Symbol
Variations
Applicable Program Areas
Operands
Operand Specifications
1206
Delays execution of the rest of the block program until the specified time has
elapsed. Execution will be continued from the next instruction after
TIMW(813)/TIMWX(816) when the timer times out.
PV Refresh Method: BCD
TIMW(813)
N
SV
PV Refresh Method: Binary
TIMWX(816)
SV
Variations
Always Executed in Block Program
Block program areas
OK
Note TIMW(813)/TIMWX(816) must be used in block programming regions even
within subroutines.
N: Timer Number
BCD:
0 to 4095 (decimal)
Binary: 0 to 4095 (decimal)
S: Set Value
BCD:
#0000 to #9999 (BCD)
Binary: &0 to &65535 (decimal)
#0000 to #FFFF (hex)
Area
CIO Area
Work Area
Holding Bit Area
Auxiliary Bit Area
Timer Area
Counter Area
DM Area
EM Area without bank
EM Area with bank
Indirect DM/EM
addresses in binary
Indirect DM/EM
addresses in BCD
N: Timer number
SV: Set value
N
N: Timer number
SV: Set value
Step program areas
OK
N
---
---
---
---
0000 to 4095
---
---
---
---
---
---
Section 3-32
Subroutines
Interrupt tasks
OK
Not allowed.
SV
CIO 0000 to CIO 6143
W000 to W511
H000 to H511
A000 to A447
A448 to A959
T0000 to T4095
C0000 to C4095
D00000 to D32767
E00000 to E32767
En_00000 to En_32767
(n = 0 to C)
@ D00000 to @ D32767
@ E00000 to @ E32767
@ En_00000 to
@ En_32767
(n = 0 to C)
*D00000 to *D32767
*E00000 to *E32767
*En_00000 to *En_32767
(n = 0 to C)