10-8-2 Connection Status for DST1 Series

Status
00:0001
Normal communications
01:0001
Safety I/O Connection
Timeout
01:0105
Configuration Owner Error The Safety Slave was configurated from a configuration tool or Safety
01:0106
Output connection Owner
Error
01:0110
Device Not Configurated
01:0113
No. of Connections Error
01:0114
Vendor ID or Program
Code Error
01:0115
Device Type Error
01:0116
Revision Error
218
The Safety I/O connection status is normal.
The Safety I/O connection has timed out. Check the following items.
• Do all nodes have the same baud rate?
• Is the cable length correct (trunk lines and branch lines)?
• Is the cable disconnected or slack?
• Is the terminating resistance only on both ends of the main line?
• Is there a lot of noise?
• Is the network bandwidth allocation suitable?
Master at a different node address last time. Reset the Safety Slave to the
default settings and download the device parameters again.
Refer to 5-1-2 Setting Safety Connection Parameters in the DeviceNet
Safety System Configuration Manual (Z905) for information on configura-
tion owners.
The Safety Slave established output safety I/o connections with a Safety
Master at a different node address last time.
Reset the Safety Slave to the default settings and download the device
parameters again.
Refer to 5-1-2 Setting Safety Connection Parameters in the DeviceNet
Safety System Configuration Manual (Z905) for information on output con-
nection owners.
The Safety Slave has not been configurated. Download the device param-
eters to the Safety Slave.
The setting for the number of safety I/O connections exceeds the upper
limit supported by the Safety Slave. Adjust the Safety Connection setting
for the relevant Safety Master.
The device data (vendor ID or product code) for the device on the Configu-
rator and the device used in the actual system does not match.
• Use Safety Slave Verification (Device
that the device in the system and the device registered to the Safety Mas-
ter match.
• If they do match, delete then re-register the connections registered to the
Safety Master.
The device data (device type) for the device on the Configurator and the
device used in the actual system does not match.
• Use Safety Slave Verification (Device
that the device in the system and the device registered to the Safety Mas-
ter match.
• If they do match, delete then re-register the connections registered to the
Safety Master.
The device data (revision) for the device on the Configurator and the
device used in the actual system does not match.
• Use Safety Slave Verification (Device
that the device in the system and the device registered to the Safety Mas-
ter match.
• If they do match, delete then re-register the connections registered to the
Safety Master.
Countermeasure
Parameter
Parameter
Parameter
Section 10-8
Verify) to check
Verify) to check
Verify) to check