Installation
3-1-2
Mounting to the Control Panel
Note
• Use the NE1A-series Controller in an enclosure with IP54 protection or
higher according to IEC/EN 60529.
• Use DIN Track (TH35-7.5/TH35-15 according to IEC 60715) to mount the
NE1A-series Controller in the control panel. Mount the Controller to the
DIN Track using PFP-M End Plates (not included with the NE1A-series
Controller) to prevent it from falling off the DIN Track because of vibration.
• Provide sufficient space around the NE1A-series Controller, at least 5 mm
at the sides and at least 50 mm at the top and bottom, for ventilation and
wiring.
5 mm min.
The NE1A-series Controller can be mounted only to DIN Track. Do not screw
the Controller to the control panel.
Wiring duct
5 mm min.
Wiring duct
Section 3-1
50 mm min.
35-mm DIN Track
End Plate
Model: PFP-M
50 mm min.
33