Function Block: Off-Delay Timer - Omron NE1A-SCPU01 - 2006 Operation Manual

Safety network controller
Table of Contents

Advertisement

Command Reference: Function Blocks
Timing Chart
Input1
(Pair1-NO)
Input2
(Pair1-NC)
Input3
(Pair2-NO)
Input4
(Pair2-NC)
Output
Enable
Discrepancy
Error Pair1
Discrepancy
Error Pair2
Fault
Present
6-5-7

Function Block: OFF-delay Timer

Diagram
General Description
Set Parameters
148
Idle to RUN
500 ms
The OFF-delay Timer function block performs a timer operation for an OFF
delay set in 10-ms increments. The range for this delay is from 0 ms to 300 s.
Parameter
OFF-delay Time
0 to 300 s in 10-ms increments
The OFF-delay time must be equal to or greater than the NE1A-series Con-
troller's cycle time.
500 ms
Discrepancy
Time
Setting range
Section 6-5
500 ms
Default setting
0 ms