Setting and Monitoring Safety Output Terminals: Outputs (NE1A-SCPU01)
Explicit message
Service
Read Safety
Read
Output Normal
Flag
Read Safety
Read
Output Error
Information Cause
Read AND of
Read
Safety Output
Normal Flags
Monitoring Test Output Terminals: NE1A-SCPU01
Explicit message
Service
Read Test Output
Read
Normal Flag
Read Test Output
Read
Error Information
Cause
Read OR of Test
Read
Output Normal
Flags
252
Function
Ser-
vice
code
Reads the normal flag status
0E hex
of the number (1 to 8) speci-
fied by the Instance ID.
Reads the cause for the nor-
0E hex
mal flag of the number (1 to
8) specified by the Instance
ID being OFF.
Reads the logical AND of the
0E hex
normal flag status for all
outputs 1 to 8.
Function
Ser-
vice
code
Reads the normal flag status
0E hex
of the test output (1 to 4)
specified by the Instance ID.
Reads the cause for the
0E hex
normal flag of the test output
(1 to 4) specified by the
Instance ID being OFF
(error).
Reads the logical OR of the
0E hex
normal flag status for all
outputs 1 to 4.
Command
Class
In-
At-
Data size
stance
trib-
ID
ID
ute ID
3B
01 to
05 hex
---
hex
08 hex
3B
01 to
6E hex ---
hex
08 hex
3C
01 hex
05 hex
---
hex
Command
Class
In-
At-
Data size
stance
trib-
ID
ID
ute ID
307
01 to
68 hex ---
hex
04 hex
307
01 to
76 hex ---
hex
04 hex
308
01 hex
69 hex ---
hex
Appendix A
Response
1 byte
00 hex: Error
01 hex: Normal
1 byte
00 hex: No error
01 hex: Invalid configuration
02 hex: Overcurrent detection
03 hex: Short-circuit detection
04 hex: High constant error
05 hex: Error in other channel of
dual channels
06 hex: Internal relay circuit
error
07 hex: Relay error
08 hex: Data error between dual
channel outputs
09 hex: Detection of short circuit
between wires
1 byte
00 hex: Error
01 hex: All normal
Response
1 byte
00 hex: Normal
01 hex: Error
1 byte
00 hex: No error
01 hex: Invalid configuration
02 hex: Overcurrent detection
05 hex: High constant error
06 hex: Undercurrent detection
1 byte
00 hex: All normal
01 hex: Error