Standard Slave Function
Setting Slave I/O
80
• Slave I/O blocks can be created for a maximum of 2 connections.
• The maximum data size for Slave I/O is 16 bytes.
• The following status information can be included in I/O data when the I/O
type of the Slave I/O is slave input.
• General Status
• Local Input Status
• Local Output Status
• Test Output/Muting Lamp Status
• If the I/O type of the Safety Slave I/O is set to Slave IN for a NE1A-series
Controller with unit version 1.0 or later, the following local I/O monitor data
can also be included in the I/O data.
• Local Input Monitor
• Local Output Monitor
Set the Slave I/O as follows:
1. Select the connection type.
2. Set the I/O tags.
3. Set additional status.
4. Set additional local I/O monitor data.
NE1A (Standard Slave)
User
program
Status data
Slave I/O
IN
Status A
Status B
Input data
OUT
Output data
Section 4-6
Connection