Omron NE1A-SCPU01 - 2006 Operation Manual page 279

Safety network controller
Table of Contents

Advertisement

Setting and Monitoring Safety Input Terminals: Inputs (NE1A-SCPU01-V1)
Explicit
Service
message
Monitor Mode for
Read
Terminal Mainte-
nance Information
Write
SV for Input Total
Read
ON Time or Contact
Operation Counter
Write
Read Input Total
Read
ON Time or Contact
Operation Counter
Reset Input Total
Reset
ON Time or Contact
Operation Counter
Read Monitor
Read
Status of Input Total
ON Time or Contact
Operation Counter
Read Safety Input
Read
Normal Flag
Read Safety Input
Read
Error Information
Cause
Read AND of Safety
Read
Input Normal Flags
Read OR of Monitor
Read
Status of Input Total
ON Times or Con-
tact Operation
Counters
244
Function
Service
Reads the monitor mode of
0E hex
maintenance information for
the input (1 to 16) specified by
the Instance ID.
Writes the monitor mode of
10 hex
maintenance information for
the input (1 to 16) specified by
the Instance ID.
Reads the SV of the total ON
0E hex
time (unit: seconds) or contact
operation counter (unit: opera-
tions) for the input (1 to 16)
specified by the Instance ID.
Writes the SV of the total ON
10 hex
time (unit: seconds) or contact
operation counter (unit: opera-
tions) for the input (1 to 16)
specified by the Instance ID.
Reads the total ON time (unit:
0E hex
seconds) or contact operation
counter (unit: operations) for
the input (1 to 16) specified by
the Instance ID.
Resets to 0 the total ON time
05 hex
(unit: seconds) or contact
operation counter (unit: opera-
tions) for the input (1 to 16)
specified by the Instance ID.
Reads the monitor status of
0E hex
the total ON time or contact
operation counter for the input
(1 to 16) specified by the
Instance ID.
Reads the normal flag status
0E hex
of the number (1 to 16) speci-
fied by the Instance ID.
Reads the cause for the nor-
0E hex
mal flag of the number (1 to
16) specified by the Instance
ID being OFF (error).
Reads the logical AND of the
0E hex
normal flag status for all inputs
1 to 16.
Reads the logical OR of the
0E hex
monitor status of the total ON
time or contact operation
counter for all inputs 1 to 16.
Command
Class
In-
At-
code
stance
tribute
ID
ID
ID
3D
01 to 10
65 hex
hex
hex
3D
01 to 10
65 hex
hex
hex
3D
01 to 10
68 hex
hex
hex
3D
01 to 10
68 hex
hex
hex
3D
01 to 10
66 hex
hex
hex
3D
01 to 10
66 hex
hex
hex
3D
01 to 10
67 hex
hex
hex
3D
01 to 10
04 hex
hex
hex
3D
01 to 10
6E hex
hex
hex
3E
01 hex
05 hex
hex
3E
01 hex
72 hex
hex
Appendix A
Response
Data size
---
1 byte
00 hex: Total ON time
mode
01 hex: Contact operation
counter mode
1 byte
---
00 hex: Total
ON time mode
01 hex: Contact
operation
counter mode
---
4 bytes
0000 0000 to FFFF FFFF
hex (0 to 4,294,967,295)
4 bytes
---
0000 0000 to
FFFF FFFF hex
(0 to
4,294,967,295)
---
4 bytes
0000 0000 to FFFF FFFF
hex (0 to 4,294,967,295)
---
---
?
1 byte
00 hex: In range
01 hex: Out of range (over
monitor value)
?
1 byte
00 hex: Error
01 hex: Normal
---
1 byte
00 hex: No error
01 hex: Invalid configura-
tion
02 hex: Test signal error
03 hex: Internal circuit
error
04 hex: Discrepancy error
05 hex: Error in other
channel of dual
channels
---
1 byte
00 hex: Error
01 hex: All normal
---
1 byte
00 hex: All in range
01 hex: Input out of range
(over monitor
value)