Command Reference: Logic Functions
Fault Present Output Setting
Error Handling and Error Resetting
Timing Table
FaultPresent
The ON status is maintained in the function block, so the Output Enable signal
stays ON even if the input condition goes from ON to OFF.
The signal maintained in the function block is turned OFF when the function
block's RESET condition is turned ON.
A Fault Present output can also be used in programming.
To enable this output, select the Fault Present checkbox on the Out Point Tab
Page of the function block properties dialog box.
Input
RESET
Maximum Number of I/O points for an RS-FF Function Block
Error condition
Behavior for error detection
Output Enable
Input and
OFF
RESET are
(safety state)
active simulta-
neously.
Input
RESET
Output
Enable
Output Enable
Fault Present
Fault Present
ON
Section 6-4
Resetting the error condition
Make one of the signals inactive.