Omron NE1A-SCPU01 - 2006 Operation Manual page 168

Safety network controller
Table of Contents

Advertisement

Command Reference: Function Blocks
Optional Output Settings
Restart Signal
The outputs shown below can be used in the program. To enable either of
these outputs, select the checkbox on the Out Point Tab Page of the function
block properties dialog box.
• Static Release
• Restart Required Indication
Maximum Number of Inputs and Outputs for a Restart Logic Function
Block
The Restart signal must meet the following conditions.
350 ms min.
In NE1A-series Controllers with unit version 1.0 or later, the Low-to-High ris-
ing edge can be selected. To enable this signal, set the Reset Signal to Rising
Edge on the Parameter Tab Page of the function block properties dialog box.
Section 6-5
133