Function Block Editing
6-3
Function Block Editing
6-3-1
Function Block Parameter Settings
Input Type Settings
112
Editing of function blocks can be used to set parameters, add optional I/O,
and add comments according to the application.
The following parameters can be set for function blocks depending on the
user application. The parameters that can be set will vary from function block
to function block.
• Input type
• Discrepancy time
• Synchronization time
• Function test
• Single Channel
• Dual Channel Equivalent
• Dual Channel Complementary
• Dual Channel Equivalent (2 Pairs)
• Dual Channel Complementary (2 Pairs)
The following truth tables outline the internal evaluations performed by the
NE1A-series Controller for each type of input signal. In the tables, 0 indicates
OFF and 1 indicates ON.
Setting: Single Channel
Input 1
Output
Enable
(NC)
0
0
1
1
Setting: Dual Channel Equivalent
Input 1
Input 2
Output
Enable
(NC)
(NC)
0
0
0
1
1
0
1
1
0
0
0
1
Section 6-3
Tabs:
Function block parameters
Out point Setting, In/Out
Settings Comments