Switch Settings - Omron NE1A-SCPU01 - 2006 Operation Manual

Safety network controller
Table of Contents

Advertisement

Nomenclature and Functions
2-1-3

Switch Settings

Node Address Switches
Note
IMPORTANT
Note
Baud Rate Switch
Note
Set the DeviceNet node address using the rotary switches on the front of the
NE1A-series Controller.
Method
Two-digit decimal
number
Range
0 to 63
The node address is set to 63 at the factory.
Any node address in the setting range can be used as long as the same
address is not used by another node. If a value between 64 and 99 is set on
the rotary switches, the node address can be set using a software setting on
the Network Configurator.
• Turn OFF power to the NE1A-series Controller before setting the rotary
switches.
• Do not change the rotary switches while the power is ON. The Controller
will detect this as a change in the configuration and will switch to ABORT
State.
• A node address duplication error will occur if the same address is set for
more than one node. Communications will not start if this error occurs.
• Use a small flat-blade screwdriver to set the rotary switches, being careful
not to scratch them.
• Refer to 4-1 Initial Setting for software setting procedures.
The DeviceNet baud rate is set using the DIP switch on the front of the NE1A-
series Controller. The baud rate settings are shown in the following table:
1
2
OFF
OFF
ON
OFF
OFF
ON
ON
ON
ON or
ON or
OFF
OFF
ON or
ON or
OFF
OFF
Note The baud rate is set to 125 kbit/s at the factory.
Refer to 4-1 Initial Setting for software setting procedures.
Pin
3
4
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON or
ON
OFF
Section 2-1
Baud rate
125 kbit/s
250 kbit/s
500 kbit/s
Software setting
Automatic baud rate
detection
23

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ne1a-scpu02 - 2006Ne1a-scpu01Ne1a-scpu01-v1Ne1a-scpu02

Table of Contents