Common Functions
Monitoring Operations from the Network Configurator
92
If the alarm threshold (Threshold Maintenance Counter) is set to 0, the Con-
troller will not compare the count or time PV to the alarm threshold SV.
Any of the following methods can be used to monitor the number of contact
operations in the local input status, test output status, or local output status.
1. Select the device and select Device – Maintenance information from the
menu bar.
2. Select the device and click the toolbar's Maintenance Button.
3. Select the device, right-click that device, and select Maintenance infor-
mation from the popup menu.
4. Select the device, select Device – Monitor from the menu bar, and click
the Maintenance Tab in the displayed window.
5. Select the device, click the toolbar's Device Monitor Button, and click the
Maintenance Tab in the displayed window.
6. Select the device, right-click that device, select Monitor from the popup
menu, and click the Maintenance Tab in the displayed window.
Section 5-1