Pay attention to the temperature for devices with a PFA
coating (conductive)
The difference in temperature between the outer and inner side of the flange may not
exceed 60 °C (140 °F).
If necessary, use external insulation.
1
 4
Difference in temperature between outer and inner side of flange
1
Insulation
A
Temperature of flange, outer side
B
Temperature of flange, inner side, for PFA (conductive) maximum 230 °C (446 °F)
C
Difference in temperature for PFA (conductive) maximum 60 °C (140 °F)
5.1.2

Take switch point into consideration

The following are typical switch points, depending on the orientation of the point level
switch.
Water +23 °C (+73 °F)
Minimum distance between the fork tip and the tank wall or pipe wall:
10 mm (0.39 in)
A
D
 5
Typical switch points. Unit of measurement mm (in)
A
Installation from above
B
Installation from below
C
Installation from the side
D
Switch point
5.1.3

Take viscosity into consideration

Low viscosity
Low viscosity, e.g. water: < 2 000 mPa⋅s
It is permitted to position the tuning fork within the installation socket.
A
B
B
B
D
Mounting
-
=
A
C
C
C
D
A0042298
A0044069
13