Mounting

12
 2
Handling the device during transportation
5
Mounting
Mounting instructions
• Any orientation for device with short pipe up to approx. 500 mm (19.7 in)
• Vertical orientation from above for device with long pipe
• Minimum distance between the fork tip and the tank wall or pipe wall: 10 mm (0.39 in)
 3
Installation examples for a vessel, tank or pipe
1
Temperature spacer/pressure-tight feedthrough (optional) for tank with insulation and/or high process
temperatures
5.1

Mounting requirements

5.1.1

Take switch point into consideration

The following are typical switch points, depending on the orientation of the point level
switch.
Water +23 °C (+73 °F)
Minimum distance between the fork tip and the tank wall or pipe wall:
10 mm (0.39 in)
Liquiphant FTL51B HART
1
A0034846
A0037879
Endress+Hauser