Technical data

14.1

Input

14.1.1

Measured variable

Level (point level), MAX or MIN safety
14.1.2

Measuring range

Depends on the installation location and the pipe extension ordered
Maximum sensor length 6 m (20 ft)
14.2

Output

14.2.1

Output and input variants

Electronic inserts
2-wire AC (FEL61)
• Two-wire AC version
• Switches the load directly into the power supply circuit via an electronic switch.
3-wire DC-PNP (FEL62)
• Three-wire DC version
• Switches the load via the transistor (PNP) and separate connection, e. g. in conjunction
with programmable logical controllers (PLC)
• Ambient temperature –60 °C (–76 °F), optionally available to order
Low-temperature electronic inserts are marked LT
Universal current connection, relay output (FEL64)
• Switches the loads via 2 potential-free changeover contacts
• Ambient temperature –60 °C (–76 °F), optionally available to order
Low-temperature electronic inserts are marked LT
Direct current connection, relay output (FEL64DC)
• Switches the load via 2 potential-free changeover contacts
• Ambient temperature –60 °C (–76 °F), optionally available to order
Low-temperature electronic inserts are marked LT
PFM output (FEL67)
• For separate switching device (Nivotester FTL325P, FTL375P)
• PFM signal transmission; current pulses are superimposed on the power supply along
the two-wire cabling
• Ambient temperature –50 °C (–58 °F), optionally available to order
The low-temperature electronic inserts are marked LT
2-wire NAMUR > 2.2 mA/<  1.0 mA (FEL68)
• For separate switching device, e. g. Nivotester FTL325N
• Signal transmission H-L edge 2.2 to 3.8/0.4 to 1.0 mA as per IEC 60917-5-6 (NAMUR)
on two-wire cable
• Ambient temperature –50 °C (–58 °F), optionally available to order
Low-temperature electronic inserts are marked LT
2-wire density (FEL60D) for density measurement
Connection to Density Computer FML621
For more information, see the Technical Information for density measuring
technology.
Technical data
55