Mounting Requirements - Endress+Hauser Liquiphant FTL51B Brief Operating Instructions

Hide thumbs Also See for Liquiphant FTL51B:
Table of Contents

Advertisement

Mounting
5
Mounting
Mounting instructions
• Any orientation for compact version or version with a pipe length of up to
500 mm (19.7 in)approx.
• Vertical orientation from above for device with long pipe
• Minimum distance between the tuning fork and the tank wall or pipe wall: 10 mm (0.39 in)
 2
Installation examples for a vessel, tank or pipe
5.1

Mounting requirements

5.1.1
Take switch point into consideration
The following are typical switch points, depending on the orientation of the point level switch.
Water +23 °C (+73 °F)
Minimum distance between the tuning fork and the tank wall or pipe wall:
10 mm (0.39 in)
8
Liquiphant FTL51B HART
A0037879
Endress+Hauser