Figure 5-2 Multiple STSs (CVC/DVC)
Procedure (DQS Series and 8DJH Series)
On the LCD of the relay, choose 05.Settings > 52.Settings to set the value of
Auto ReClose T.
Parameter
Auto ReClose T
Procedure (CGM.3 Series)
On the LCD of the relay, choose 1.4.2 VOLTAGE_PRESENCE_ABSENCE >
VOLTAGE_PRESENCE_ABSENCE to set the values of Presence_Time and Auto
ReClose T.
Parameter
Presence_Time
Auto ReClose T
Issue 02 (2023-09-30)
STS1 Value (s)
15
NO TE
● n indicates the number of STSs connected to the same main transformer.
● For details about how to operate on the LCD of the relay, see the user manual of the
PA620 delivered with the product.
STS1 Value (s)
15
15
NO TE
● n indicates the number of STSs connected to the same main transformer.
● For details about how to operate on the LCD of the relay, see the user manual of the
RPA-220 delivered with the product.
Copyright © Huawei Technologies Co., Ltd.
5 Human-Machine Interaction
n Value (s)
STS
15 + 2 x (n-1)
n Value (s)
STS
15 + 2 x (n-1)
15 + 2 x (n-1)