1.
2.
Step 2 Tools: Phillips insulated torque screwdriver and insulated torque socket wrench
Step 3 Power-off: Turn off 1FB3.
----End
Procedure
Step 1 Open the sealing plate of LV PANEL A based on the silk screen.
Figure 6-52 Opening the sealing plate of LV PANEL A
Step 2 Remove the cables from the main control module and record their positions.
Step 3 Remove the old main control module.
Issue 02 (2023-09-30)
Back up the configuration file. Select a backup mode based on the site
requirements.
Method 1 (manual backup): Log in to the SmartLogger, choose Monitoring >
STS, click the Sync tab, and click Start in the Configuration file backup row
to manually back up the configuration file.
Method 2 (automatic backup): Log in to the SmartLogger, choose Monitoring
> STS, click the Sync tab, set Automatic Configuration File Backup to
Enabled, and set Automatic Backup Time to enable the automatic
configuration file backup function.
Figure 6-51 Configuration file backup
After the export is successful, click Confirm.