Figure 6-59 Removing the old measurement and control module in the MV room
Step 4 Install a new measurement and control module in the original position. Use an M6
Phillips screwdriver and tighten the screws to a torque of 5 N·m.
Step 5 Secure the new measurement and control module to the bracket. Use an M4
Phillips screwdriver and tighten the screws to a torque of 1.2 N·m.
Step 6 Reconnect the cables to the new measurement and control module based on the
cable connection records.
Step 7 Power on the measurement and control module in the reverse order of the power-
off operations.
----End
Follow-up Procedure
Step 1 Log in to the SmartLogger WebUI, choose Maintenance > Software Upgrade,
upload the STS upgrade package, select the device, and upgrade the STS to ensure
that the STS version is the same as the other STS version displayed on the
SmartLogger WebUI. If they are inconsistent, upgrade the software version to
ensure that no alarm indicating inconsistent measurement and control module
software versions is generated.
Step 2 On the SmartLogger WebUI, choose Monitoring > STS > Running Param. > O&M
Parameters, and click Start in the row of Controller location detection to
perform measurement and control module location detection and assign a
physical location to the new measurement and control module.