Huawei JUPITER-3000K-H1 Smart User Manual page 127

Transformer station
Hide thumbs Also See for JUPITER-3000K-H1 Smart:
Table of Contents

Advertisement

JUPITER-(3000K, 6000K, 9000K)-H1 Smart
Transformer Station
User Manual
Alar
Alarm
m ID
Name
2318
Fan Fault
Outside
Low-
Voltage
Cabinet B
Issue 02 (2023-09-30)
Alarm
Possible Cause
Severity
Minor
Cause ID = 1, 3, 4, 6
1. The port terminal is
in poor contact.
2. The heat exchanger
fan is faulty.
3. The power supply
to the fan is faulty.
Cause ID = 2, 5
1. The port terminal is
in poor contact.
2. The heat exchanger
fan is faulty.
3. The power supply
to the fan is faulty.
4. The maximum fan
speed is incorrectly
set.
Copyright © Huawei Technologies Co., Ltd.
6 System Maintenance
Suggestion
Cause ID = 1, 3, 4, 6
1. Check whether the cable is loose.
If yes, secure the cable.
2. Check whether the fan is faulty. If
yes, replace the fan.
3. Check whether the fan port of the
monitoring device has a 48 V
voltage. If no, replace the
monitoring device or PSU.
4. If the fault persists, contact your
dealer or technical support.
Cause ID = 2, 5
1. Check whether the cable is loose.
If yes, secure the cable.
2. Check whether the fan is faulty. If
yes, replace the fan.
3. Check whether the fan port of the
monitoring device has a 48 V
voltage. If no, replace the
monitoring device or PSU.
4. Check whether the maximum fan
speed is set correctly.
5. If the fault persists, contact your
dealer or technical support.
119

Advertisement

Table of Contents
loading

This manual is also suitable for:

Jupiter-6000k-h1 smartJupiter-9000k-h1 smart

Table of Contents