JUPITER-(3000K, 6000K, 9000K)-H1 Smart
Transformer Station
User Manual
Figure 6-31 Position of the oil surface temperature controller
(1) Oil surface temperature controller
Power-Off
1.
2.
3.
Procedure
Step 1 Rotate the cover counterclockwise to remove the glass cover.
Step 2 Take out the foam.
Step 3 Rotate the cover clockwise to reinstall the glass cover. Ensure that the white
pointer is on the left and the red pointer is on the right.
Step 4 Rotate the knob to put the red and white pointers together.
Figure 6-32 Operating an oil temperature indicator
----End
Issue 02 (2023-09-30)
(Optional) Shut down the UPS inverter 3UI. Perform this operation when the
UPS has been installed.
Turn off the ACB (1QA) of LV PANEL A or the ACB (2QA) of LV PANEL B.
Turn off the VCB in the MV room.
Copyright © Huawei Technologies Co., Ltd.
6 System Maintenance
(2) Pressure relief valve (thermo-bulb
position)