No.
4
5
Container Check
No.
1
2
3
4
LV Panel Check
No.
1
2
3
Issue 02 (2023-09-30)
Check Item
Acceptance Criteria
Cable routing
● Electric and extra low voltage (ELV) cables are
routed separately.
● Cables are neat and tidy.
● Cable tie joints are evenly cut without burrs.
● Cables are placed properly with slack at bending
points to avoid stress.
● Cables are routed neatly without twists or crossovers
in the cabinet.
Container
The container is clean and tidy inside, without any
cleanness
unnecessary cables, cable ends, terminals, or tools. No
garbage is found outside the equipment.
Check Item
Acceptance Criteria
Installation
● The installation meets the design requirements.
● The container is level, and each door opens
normally.
Exterior
The container surface is free from cracks, dents, and
scratches. If the paint flakes off, repair the damaged
paint.
Accessory
The quantity and positions of external accessories
installed meet design requirements.
Label
All labels are correct, clear, and complete.
Check Item
Acceptance Criteria
Circuit
The ACBs and MCCBs are turned off. The settings of
breaker
the circuit breakers must match that provided by the
user.
Copper bar
The copper bars are not deformed, and no foreign
objects are placed on the copper bars.
Fuse switch-
Measure the fuse resistance. The resistance of three
disconnector
phases should be small and their resistance should be
close.