Huawei JUPITER-3000K-H1 Smart User Manual page 131

Transformer station
Hide thumbs Also See for JUPITER-3000K-H1 Smart:
Table of Contents

Advertisement

JUPITER-(3000K, 6000K, 9000K)-H1 Smart
Transformer Station
User Manual
Alar
Alarm
m ID
Name
2328
Smoke
Alarm in
Medium-
Voltage
Room
2329
Dual
Smoke
Sensor
Tripping in
Medium-
Voltage
Room
2330
Smoke
Sensor
Fault in
Medium-
Voltage
Room
Issue 02 (2023-09-30)
Alarm
Possible Cause
Severity
Minor
1. A fire occurs inside
the STS.
2. The sensor
generates a false
alarm.
Major
A fire occurs inside the
STS.
Warning
Smoke sensor 1/2 in
the medium-voltage
room is faulty.
Copyright © Huawei Technologies Co., Ltd.
6 System Maintenance
Suggestion
1. Check whether a fire occurs
onsite. If a fire occurs in the low-
voltage cabinet, switch off the
low-voltage and medium-voltage
circuit breakers immediately. If a
fire occurs in the ring main unit,
switch off the circuit breaker in
the booster station.
2. If the fault persists, contact your
dealer or technical support.
1. Check whether a fire occurs
onsite. If a fire occurs in the low-
voltage cabinet, switch off the
low-voltage and medium-voltage
circuit breakers immediately. If a
fire occurs in the ring main unit,
switch off the circuit breaker in
the booster station.
2. If the fault persists, contact your
dealer or technical support.
1. Check whether the smoke sensor
is faulty. If yes, replace the sensor.
2. If the fault persists, contact your
dealer or technical support.
123