Huawei JUPITER-3000K-H1 Smart User Manual page 89

Transformer station
Hide thumbs Also See for JUPITER-3000K-H1 Smart:
Table of Contents

Advertisement

JUPITER-(3000K, 6000K, 9000K)-H1 Smart
Transformer Station
User Manual
Step 4 The solar inverters are running and feeding current.
----End
Supplying Power to the PID (When the IMD Is Configured)
Step 1 Set the IMD device access status of PID1 to Disable. After PID1 runs, observe that
the HM LED on the IMD in LV PANEL A is off.
Step 2 Set the IMD device access status of PID1 to Enable, and set the running periods of
the IMD and PID. (You can set the IMD period running time to 60 minutes and the
PID period running time to 60 minutes.)
Step 3 During the IMD running cycle (The running status of the PID and IMD can be
switched through the SmartLogger.) and observe the running status of the IMD in
the LV PANEL A.
Step 4 Set the IMD device access status of PID2 to Disable. After PID2 runs, observe that
the HM LED on the IMD in LV PANEL B is off.
Step 5 Set the IMD device access status of PID2 to Enable, and set the running periods of
the IMD and PID. (You can set the IMD period running time to 60 minutes and the
PID period running time to 60 minutes.)
Step 6 During the IMD running cycle (The running status of the PID and IMD can be
switched through the SmartLogger.) and observe the running status of the IMD in
the LV PANEL B.
----End
Checking the STS with Loads
Step 1 Check the current displayed on the multimeter of LV PANEL A and on the
electronic tripper of the ACB. The currents of the three phases should be equal or
close.
Step 2 Check the current displayed on the multimeter of LV PANEL B and on the
electronic tripper of the ACB. The currents of the three phases should be equal or
close.
Step 3 Check the current displayed on the protection device of the MV cabinet. The
currents of the three phases should be equal or close.
----End
Issue 02 (2023-09-30)
NO TE
The normal running status of the IMD is as follows:
● The green LED WR is steady on.
● Yellow LED light strip: Eight LEDs showing the current actual insulation resistance (10
kΩ to 2 MΩ).
● The HM LED indicator blinks slowly or fast.
Copyright © Huawei Technologies Co., Ltd.
4 Power-On
81

Advertisement

Table of Contents
loading

This manual is also suitable for:

Jupiter-6000k-h1 smartJupiter-9000k-h1 smart

Table of Contents