JUPITER-(3000K, 6000K, 9000K)-H1 Smart
Transformer Station
User Manual
Feature Parameters
Item
JUPITER-30
00K-H1
Transformer
Oil-immersed
type
Transformer
ONAN
cooling
type
Transformer
Mineral oil
oil type
Transformer
Dy11
vector
group
MV
SF
, 12–40.5 kV, 630 A, 50 Hz/60 Hz, three feeders (CVC/CCV or DVC/DCV), 20
6
switchgear
kA/3s, 50/51, 50N/51N, 50BF (optional), 50G/51G (optional)
LV room
1 x ACB
(4000
A/800 V/
3P), 11 x
MCCB (400
A/800
V/3P)
Auxiliary
Specifications
transformer
● 5 kVA, Ii0, 800 V/230 V/127 V
● 50 kVA, Dyn11, 800 V/400 V
● 50 kVA, Dyn11, 800 V/220 V
Issue 02 (2023-09-30)
JUPITER-60
JUPITER-9000K-H1
00K-H1
Dy11-y11
2 x ACB
2 x ACB (4000 A/800 V/3P), 30 x MCCB (400 A/800
(4000
V/3P)
A/800 V/
3P), 22 x
MCCB (400
A/800
V/3P)
Copyright © Huawei Technologies Co., Ltd.
8 Technical Specifications
220

Advertisement

Table of Contents
loading

This manual is also suitable for:

Jupiter-6000k-h1 smartJupiter-9000k-h1 smart

Table of Contents