Huawei JUPITER-3000K-H1 Smart User Manual page 195

Transformer station
Hide thumbs Also See for JUPITER-3000K-H1 Smart:
Table of Contents

Advertisement

JUPITER-(3000K, 6000K, 9000K)-H1 Smart
Transformer Station
User Manual
No.
Running Parameter
17
Heater startup
humidity in low-
voltage cabinet
18
Heat exchanger fan
startup humidity in
low-voltage cabinet
19
Alarm threshold for
high temperature in
low-voltage cabinet
20
Tripping threshold
for high temperature
in low-voltage
cabinet
21
Heat exchanger in
medium-voltage
room
22
Heat exchanger fan
startup humidity in
medium-voltage
room
23
Alarm threshold for
high temperature in
medium-voltage
room
24
Tripping threshold
for high temperature
in medium-voltage
room
25
Auxiliary transformer
type
Issue 02 (2023-09-30)
Description
Humidity range: 15% to
100%
Humidity range: 15% to
100%
Temperature range: 0°C–
85°C
– Temperature range: 0°C–
85°C
– The setting must be
greater than or equal to
the alarm threshold for
high temperature.
Select Yes or No based on
the actual configuration.
This parameter is displayed
when Heat exchanger in
medium-voltage room is
set to Yes.
Temperature range: 0°C–
85°C
– Temperature range: 0°C–
85°C
– The setting must be
greater than or equal to
the alarm threshold for
high temperature.
Select Single-phase for the
3 kVA and Three-phase for
the 50 kVA.
Copyright © Huawei Technologies Co., Ltd.
6 System Maintenance
Associated
Associated
Teleindication
Telemetering
Signal
Signal
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
187