JUPITER-(3000K, 6000K, 9000K)-H1 Smart
Transformer Station
User Manual
No.
4
5
6
7
8
9
10
Transformer Check
No.
1
2
3
4
5
6
Issue 02 (2023-09-30)
Check Item
Acceptance Criteria
Surge
The SPD indicator is green.
protective
device (SPD)
(Optional)
The multimeter has no reading.
Multimeter
Cable
The bolts for installing the cables are tightened and the
cables are not loose.
Cable hole
Cable holes are sealed.
sealing
Component
All components are intact.
Foreign object
Foreign objects in the LV panels, such as tools and
remaining materials, are removed.
Residual
Use the test button to verify that the circuit breaker
current circuit
works properly.
breaker
Check Item
Acceptance Criteria
Exterior
The transformer surface is free from cracks, dents, and
scratches.
Oil leakage
No oil leakage occurs on the transformer surface.
Oil
The reading of the transformer oil temperature
temperature
indicator is close to the ambient temperature. The
cover of the oil temperature indicator is installed
securely. The surface is clean and the glass is not
damaged. The temperature measurement loop is
complete and intact.
Oil level
The reading of the transformer oil level gauge is
consistent with the oil level and temperature curves.
Pressure relief
The fuse link of the pressure relief valve has been
valve
removed, and the pressure relief valve takes no action.
Gas relay
● There is no gas inside the gas relay. If there is a
small amount of gas, the air can be exhausted
through the gas release plug.
● The butterfly valve is open.