JUPITER-(3000K, 6000K, 9000K)-H1 Smart
Transformer Station
User Manual
Alar
Alarm
m ID
Name
2354
Transforme
r Oil Level
Low
2355
Transforme
r Oil
Temperatur
e High
Issue 02 (2023-09-30)
Alarm
Possible Cause
Severity
Minor
1. The transformer
leaks oil or seeps
oil for a long time.
2. After oil is drained
due to
maintenance,
repair, or tests, the
transformer is not
refilled to the
normal level in
time.
3. A false low oil level
alarm is generated
due to the
secondary loop.
4. Oil leaks into the
capsule.
Minor
1. The transformer is
overloaded.
2. A false alarm is
generated due to
the secondary loop.
3. The oil surface
thermometer is
faulty.
Copyright © Huawei Technologies Co., Ltd.
6 System Maintenance
Suggestion
1. Check the secondary loop for false
actions. If the relay action is
correct, refill oil to the
transformer.
2. Check whether the capsule is
damaged. If yes, replace the
capsule.
3. If the fault persists, contact your
dealer or technical support.
1. Check whether the transformer is
overloaded. If yes, the high oil
temperature alarm is generated in
some scenarios.
2. Check whether a false alarm is
generated based on the cable
connection of the secondary loop.
3. Check whether the temperature
on the monitoring device is
consistent with that on the oil
surface thermometer. If no, rectify
the fault on the oil surface
thermometer.
4. If the fault persists, contact your
dealer or technical support.