Alar
Alarm
m ID
Name
2344
Transforme
r
Overcurrent
Protection
Action
2345
Transforme
r Zero-
Sequence
Overvoltag
e
Protection
Action
2346
Transforme
r Zero-
Sequence
Overcurrent
Protection
Action
Issue 02 (2023-09-30)
Alarm
Possible Cause
Severity
Major
The transformer is
overloaded or a short
circuit occurs on the
low-voltage side but
the low-voltage circuit
breaker takes no
action.
Major
The three-phase
voltage of the
medium-voltage
power grid is
unbalanced or the
single-phase cable is
grounded.
Major
The three-phase
current of the
medium-voltage
power grid is
unbalanced or the
single-phase cable is
grounded.
Copyright © Huawei Technologies Co., Ltd.
6 System Maintenance
Suggestion
1. Check and download the relay
protection event records of the
ring main unit onsite, determine
the phase where the short circuit
occurs, locate the fault point, and
rectify the fault.
2. Rectify the fault before switching
on the medium-voltage circuit
breaker.
3. If the fault persists, contact your
dealer or technical support.
1. Check and download the relay
protection event records of the
ring main unit onsite, compare the
records with the monitoring data
of the booster station, identify the
fault cause, and rectify the fault.
2. Check whether the medium-
voltage cable is grounded. If yes,
repair the cable.
3. Rectify the fault before switching
on the medium-voltage circuit
breaker.
4. If the fault persists, contact your
dealer or technical support.
1. Check and download the relay
protection event records of the
ring main unit onsite, compare the
records with the monitoring data
of the booster station, identify the
fault cause, and rectify the fault.
2. Check whether the medium-
voltage cable is grounded. If yes,
repair the cable.
3. Rectify the fault before switching
on the medium-voltage circuit
breaker.
4. If the fault persists, contact your
dealer or technical support.