3.12.3. How to set the test mode (flow simulated output)
Description
This function sets simulated output for the volume flow rate and checks
each output (LED display, analog output, DO output).
The output at the time of setting is set as the initial value, changes according to
the time of the set "tracking time" until it reaches the input value (simulated flow
rate target value), and becomes a constant value output according to the input
value.
Each output changes according to the variation of the simulated flow rate output.
When operating in test mode, "TEST" will blink on the first row of the LED.
Settings
Test mode switching
Tracking time: Time to reach simulated flow target value (input value mentioned
Input data
Setting range
Test mode switching: Do not execute (NO), Execute (USED)
Tracking time
Input data
*When setting the follow-up time, set the damping in "
This operation changes the output of the analog outputs AO, DO1 and DO2 according to the settings.
Confirm in advance that you want to change each output.
After testing, be sure to change the setting back to "Do not execute". Otherwise, the input value output state will be saved
until the power is turned off.
For specific key operations, refer to the example operations indicated below.
Operation (example)
Display and keystrokes
1
Measurement display
Press and hold the ○ key
2
○ Key
3
○ Key
4
○ Key
5
○ Key
6
○ Key
7
○ Key
:
Enables or disables test mode.
above)
:
Simulated flow target value (percentage of full
scale).
:
0 to 900 seconds
:
±120%
Connect the ammeter to the AO cable. Cable colors: AO+ (green), AO- (brown)
Press and hold the ○ key to go to Display 2.
Press the ▽ key four times and select "MENT".
Press and hold the ○ key to go to Display 3.
Press the ○ key twice to go to Display 4.
Displays "MENT TEST".
Press and hold the ○ key to go to Display 5.
Test mode switching: NO, USED
Use the △▽ keys and set USED to activate test mode.
Press the ○ key to go to Display 6.
Tracking time: 0 to 900 sec
Press the △▽ keys to set the values.
Press the ○ key to go to Display 7.
Input data: -120% to 120%
Press the △▽ keys to set the values.
Press the ○ key to go to Display 8.
" to 0 sec.