Setting When The Power Is Turned On For The First; Time - Fuji Electric FSZ Instruction Manual

Integral ultrasonic flowmeter s-flow
Table of Contents

Advertisement

3.4. Setting when the power is turned ON for the first time
Description
Sets parameters for piping and measurement fluids.
You can set and change them later in 3.8Measurement settings.
Be sure to set the following parameters before mounting the flowmeter to a pipe.
Set the accurate pipe outer diameter and wall thickness dimensions. Otherwise, performance can be impaired.
If the exact parameters are not set, there will be large measurement errors.
Wave receipt errors may also occur.
Item
1. Pipe outer diameter :
2. Pipe material
3. Pipe thickness
4. Measurement fluids :
For specific key operations, refer to the typical operation indicated below.
Operation (example)
Display and keystrokes
1
Measurement display
○ Key
2
○ Key
3
○ Key
4
○ Key
5
○ key, ○ key
6
7
○ Key
8
Measurement display
5.00 to 99.99 [mm] (Factory default: FSZ08: 13.80, FSZ15: 21.70, FSZ25: 34.00 [mm])
:
Carbon Steel, stainless steel (factory default), copper, PVC, PFA, PTFE
:
0.10 to 9.99 [mm] (factory default: FSZ 08: 2.00, FSZ 15: 2.50, FSZ 25: 3.00 [mm])
Water (factory default), seawater, fluid sound velocity
Fluid sound velocity: (Sound velocity: 1000 to 2000 [m/s])
Press the ○ key to go to Display 2.
Pipe outer diameter: 5.00 to 99.99 [mm]
Press the △▽ keys to set the values.
Press the ○ key to go to Display 3.
Pipe material: Carbon steel, stainless steel, copper, PVC,
Press the △▽ keys to set the items.
Press the ○ key to go to Display 4.
Pipe thickness: 0.10 to 9.99 [mm]
Press the △▽ keys to set the values.
Press the ○ key to go to Display 5.
Measurement fluids: Water,
Press the △▽ keys to set the items.
Select water or seawater and press the ○ key to go to Display 7.
Select the fluid sound velocity and press the ○ key to go to Display 6.
Fluid speed velocity: 1000 to 2000 [m/s]
Press the △▽ keys to set the values.
Press the ○ key to go to Display 7.
○ Key
Press the ○ key to return to the measurement display.
Description
,
,
seawater, fluid sound velocity
,
- 18 -
PFA,
,
,
,
,
(initial values)
PTFE

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fsz08Fsz15Fsz25