3.8.1. Piping parameter setting method
Description
●
Sets parameters for piping and measurement fluids.
Be sure to set the following parameters before mounting the flowmeter to a pipe.
●
Set the accurate pipe outer diameter and wall thickness dimensions. Otherwise, performance can be impaired.
●
If the exact parameters are not set, there will be large measurement errors.
●
Wave receipt errors may also occur.
Item
1. Pipe outer diameter
2. Pipe material
3. Pipe thickness
4. Measurement fluids
5. Dynamic viscosity coefficient : (Factory default: 1.004 x 10
6. Flow direction
For specific key operations, refer to the example in
3.8.2. Key operations for measurement settings
Operation (example)
Display and keystrokes
1
Measurement display
Press and hold the ○ key
2
○ Key
3
○ Key
4
○ Key
5
○ Key
6
○ key
3.8. Measurement settings
: 5.00 to 99.99 [mm] (Factory default: FSZ08: 13.80, FSZ15: 21.70, FSZ25: 34.00 [mm])
: Carbon Steel, stainless steel (factory default), copper, PVC, PFA, PTFE
: 0.10 to 9.99 [mm] (factory default: FSZ 08: 2.00, FSZ 15: 2.50, FSZ 25: 3.00 [mm])
: Water (factory default), seawater, fluid sound velocity
Fluid sound velocity: (Sound velocity: 1000 to 2000 [m/s])
: R-L, L-R
R-L: Flow direction from right to left from the front of the flowmeter
L-R: Flow direction from left to right from the front of the flowmeter
3.8.2.
Press and hold the ○ key to go to Display 2.
Press the ▽ key twice and select "SET PIPE".
Press the ○ key to go to Display 3.
Pipe outer diameter: 5.00 to 99.99 [mm]
Press the △▽ keys to set the values.
Press the ○ key to go to Display 4.
Pipe material: Carbon steel, stainless steel, copper,
*For PP or PVDF, select "PVC".
Press the △▽ keys to set the items.
Press the ○ key to go to Display 5.
Pipe thickness: 0.10 to 9.99 [mm]
Press the △▽ keys to set the values.
Press the ○ key to go to Display 6.
Measurement fluids: Water,
Press the △▽ keys to set the items.
Select water or seawater and press the ○ key to go to Display 8.
○ key
Select the fluid sound velocity and press the ○ key to go to Display 7.
- 22 -
-6
[m
2
/s])
Description
,
,
seawater, fluid sound velocity
,
,
PVC,
PFA,
PTFE
,
,
,
(initial values)