Increasing/Decreasing Frequency Command By Remote Control - Hitachi WJ Series User Manual

Table of Contents

Advertisement

Chapter 9
9.2.13

Increasing/Decreasing Frequency Command by Remote Control

 How to increase or decrease the frequency command using an I/O input signal?
Q
 How to increase or decrease the frequency command or PID target value using an external
remote button?
Remote control function ([FUP]/[FDN]/[UDC] input terminal function)
A
 The remote control function increases or decreases the currently used frequency command
when the "Remote control Speed-UP function [FUP] (27)" or the "Remote control Speed-DOWN
function [FDN] (28)" input terminals is turned on.
 This function is enabled when the frequency command input source is set to one of the
following configurations. It cannot be used in the case of analog inputs or jogging command.
- The "Frequency input source selection [A001]
- The frequency command input source is a multi-speed operation function.
- The "Frequency input source selection [A001]
"Analog command holding [AHD] (65)" input terminal is on.
 Acceleration/Deceleration time when [FUP]/[FDN] is turned on are according to the settings of
the "Acceleration time 1 setting or monitor [F002]
monitor [F003]
 If the "FUP/FDN data save enable [C101]" is set to "Save (01)", the frequency command value
adjusted by the [FUP]/[FDN] is saved in the inverter memory when the inverter power is shut off
or when the command input source is switched.
 When the "Remote control speed data clearing [UDC] (29)" input terminal is turned on, the
frequency command value adjusted by the [FUP]/[FDN] is changed back to 0 Hz or the value
originally saved before adjusted by the [FUP]/[FDN] according to the "FUP/FDN [UDC] terminal
mode selection [C104]" setting.
Code
FUP/FDN data save
[C101]
enable
FUP/FDN [UDC] terminal
[C104]
mode selection
[C001]
to
Input terminal function
[C007]
 Do not turn on/off the [FUP]/[FDW] input terminals or operate the JOG dial on the keypad
!
immediately after the power has been shut off. Doing so may result in the failure to properly save
any frequency commands that were changed.
 When [C101] is set to "Save (01)", even if the [SET] key is not pressed after changing the
frequency command values [A020]
frequency changes through monitor display [b163]" function
the changed values are automatically saved to the inverter memory when the power is shut off.
*1. "2nd-motor control [SET]" target parameter. The second control parameter is also subject to setting.
*2. For details, refer to "9.2.15
*1
".
Item
Do not save:
Save:
0 Hz: Cleared to 0 Hz.
Saved data:
Remote control Speed-UP function [FUP]:
Remote control Speed-DOWN function [FDN]:
Remote control Speed data clearing [UDC]:
*1
/[A021] to [A035], [F001], and [d001]/[d007] ("Enable
Setting Frequency Command on Frequency Monitor
*1
" is set to "Parameter setting (02)".
*1
" is set to the "Control terminal (01)" and the
*1
" and the "Deceleration time 1 setting or
Description
The command frequency increased or decreased
by the [FUP]/[FDN] function is not saved in the
inverter memory when the power is shut off or the
command input source is switched.
The command frequency increased or decreased
by the [FUP]/[FDN] function is saved in the inverter
memory when the power is shut off or the
command input source is switched.
Returns it to the saved data before [FUP]/[FDN]
adjustment.
When this terminal is turned on, the frequency
command value is increased.
When this terminal is turned on, the frequency
command value is decreased.
When this terminal is turned on, the frequency
command value is cleared. When cleared, it returns
to the value set in [C104].
*2
9-2-18
Inverter Functions
) by the JOG dial on the keypad,
".
Data
00
01
00
01
27
28
29