Hitachi WJ Series User Manual page 228

Table of Contents

Advertisement

Chapter 9
Code
PID feed-forward
[A079]
input source
selection
[A156]
PID sleep start level
[A157]
PID sleep active time
PID over deviation
[C044]
level
Turn-off level for the
[C052]
PID feedback
compare signal
Turn-on level for the
[C053]
PID feedback
compare signal
[C001]
Input terminal
to
function
[C007]
[C021]
Output terminal
[C022]
function
[C026]
Item
00 (Disable)
01 ([Ai1] terminal input (voltage input))
02 ([Ai2] terminal input (current input))
The sleep operation start level is set by
output frequency.
The sleep operation starts when [A156] or
a lower value persists for the duration of
this setting.
Outputs "Over deviation for PID control
[OD] (04)" when PID deviation equals or is
greater than this setting. Set in units of %,
with the maximum frequency being 100%.
Sets the point at which the PID feedback
comparison signal is turned OFF.
Sets the point at which the PID feedback
comparison signal is turned ON.
Disable PID [PID]:
Turn this signal ON to disable PID
calculation and enter normal frequency
operation mode.
PID integration reset [PIDC]:
Turn this signal ON to reset the integral
value of PID control to 0.
Over deviation for PID control [OD]:
This signal turns ON when the PID
deviation equals or exceeds the [C044]
setting.
PID feedback comparison [FBV]:
This signal turns ON when the PID
feedback falls outside the setting range.
9-8-2
Description
Inverter Functions
Data
00
01
02
0.00 to 590.00 (Hz)
0.0 to 25.5 (s)
0.0 to 100.0 (%)
0.0 to 100.0 (%)
0.0 to 100.0 (%)
23
24
04
31