Chapter 9
9.12.2

Outputting a Signal during Forward/Reverse Running

 How to detect information during the forward rotation of the inverter and inform the system?
Q
 How to detect information during the reverse rotation of the inverter and inform the system?
 Assigning "Forward rotation [FWR] (51)" or "Reverse rotation [RVR] (52)" to one of the output
A
terminal functions ([C021]/[C022]/[C026]) enables the inverter to output a forward/reverse
rotation signal.
 The [FWR]/[RVR] signal is not output while the voltage is being output from the inverter to the
!
motor due to DC injection braking or other reasons.
Code
[C021]
Output terminal
[C022]
function
[C026]
Output frequency
RUN command
[FW] input
RUN command
[RV] input
Forward rotation
[FWR] output
Reverse rotation
[RVR] output
Item
Forward rotation [FWR]:
This signal is output during inverter forward rotation.
Reverse rotation [RVR]:
This signal is output during inverter reverse rotation.
Forward
rotation
ON
ON
9-12-2
Inverter Functions
Description
Reverse
rotation
ON
ON
Data
51
52