Hitachi WJ Series User Manual page 235

Table of Contents

Advertisement

Chapter 9
Code
Overload restriction 1
*1
[b021]
mode selection
Overload restriction 1
*1
[b022]
active level
Overload restriction 1
*1
[b023]
action time
Overload restriction 2
[b024]
mode selection
Overload restriction 2
[b025]
active level
Overload restriction 2
[b026]
action time
[C001]
Input terminal
to
function
[C007]
Example of overload restriction function operation
Output current
Output frequency
Maximum frequency
Command frequency
[OLR] input
*1. "2nd-motor control [SET]" target parameter. The second control parameter is also subject to setting.
Item
Disable
Enable during acceleration and constant
speed
Constant speed only
Enabled during acceleration and constant
speed (Accel. during regeneration)
Sets the current value when the overload
restriction is activated.
Sets the deceleration time when the
overload restriction is activated. The
value is set to the deceleration time from
the maximum frequency to 0 Hz.
Sets the operation of Overload restriction
2, which operates when the [OLR]
terminal is ON.
The settings are similar to [b021], [b022],
and [b023].
Overload restriction selection [OLR]:
Switches overload restriction 1/2 by
turning on or off of this terminal.
Overload restriction 1
active level [b022]
Overload restriction 1
action time [b023]
9-9-2
Description
*1
Overload restriction 2
active level [b025]
Overload restriction 2
action time [b026]
*1
ON
Inverter Functions
Data
00
01
02
03
(0.20 to 2.00) × rated current (A)
(ND mode)
(0.20 to 1.50) × rated current (A)
(LD mode)
0.1 to 3000.0 (s)
00 to 03
(0.20 to 2.00) × rated current (A)
(ND mode)
(0.20 to 1.50) × rated current (A)
(LD mode)
0.1 to 3000.0 (s)
39