Chapter 18
Code
Name
Manual torque
A042
boost value, 1st-
motor
0.0 to 20.0 (%)
Manual torque
A242
boost value, 2nd-
motor
Manual torque
A043
boost peak
speed, 1st-motor
Manual torque
0.0 to 50.0 (%)
boost peak
A243
speed, 2nd-
motor
Control mode
00: [V/f] Constant torque
A044
selection, 1st-
motor
01: [V/f] Reducing torque
Control mode
02: [V/f] Free V/f (IM)
A244
selection, 2nd-
03: Sensorless vector control
motor
Output voltage
A045
20 to 100 (%)
gain, 1st-motor
Output voltage
A245
20 to 100 (%)
gain, 2nd-motor
Automatic torque
boost voltage
A046
0 to 255
compensation
gain, 1st-motor
Automatic torque
boost voltage
A246
0 to 255
compensation
gain, 2nd-motor
Automatic torque
boost slip
A047
0 to 255
compensation
gain, 1st-motor
Automatic torque
boost slip
A247
0 to 255
compensation
gain, 2nd-motor
00: Disable
DC braking
01: Enable
A051
selection
02: Enable (Output frequency
DC braking
A052
0.00 to 60.00 (Hz)
frequency
DC braking delay
A053
0.0 to 5.0 (s)
time
0 to 100 (%) (Normal duty (ND))
A054 DC braking force
0 to 70 (%) (Low duty (LD))
DC braking active
A055
0.0 to 60.0 (s)
time at stop
DC braking
00: Edge operation
A056
operation
01: Level operation
method selection
DC braking force
0 to 100 (%) (Normal duty (ND))
A057
at start
0 to 70 (%) (Low duty (LD))
DC braking active
A058
0.0 to 60.0 (s)
time at start
2.0 to 15.0 (kHz)
Carrier frequency
(Normal duty (ND))
A059
during DC
2.0 to 10.0 (kHz)
*4
braking
(Low duty (LD))
*2. The default settings when initialize by setting 00/01/03 to "Initialize data selection [b085]".
*4. This parameter is a dummy parameter. User setting is disabled. Carrier frequency in DC braking is shared with
"Carrier frequency [b083]". In addition, if data is written within the data range by Modbus communication, no
error will occur.
List of Parameters/Modbus Coil/Register Numbers
Data range
characteristics (IM)
characteristics (IM)
(SLV) (IM) (Selectable only
at ND)
< [A052])
18-2-7
Change
Initial
Set
during
value
value
Register No.
running
123Ch
1.0/
1.0/
*2
5.0
223Ch
123Dh
5.0
223Dh
00
×
123Eh
00
×
223Eh
100
123Fh
100
223Fh
100
1240h
100
2240h
100
1241h
100
2241h
00
1245h
0.50
1246h
0.0
1247h
50
1248h
0.5
1249h
01
124Ah
0
124Bh
0.0
124Ch
5.0
124Dh
Modbus communication
Data Range
Resolution
0 to 200
0.1
0 to 200
0.1
0 to 500
0.1
0 to 500
0.1
0 to 3
-
0 to 3
-
20 to 100
1
20 to 100
1
0 to 255
1
0 to 255
1
0 to 255
1
0 to 255
1
0 to 2
-
0 to 6000
0.01
0 to 50
0.1
0 to 100 (ND)
1
0 to 70 (LD)
0 to 600
0.1
0 to 1
-
0 to 100 (ND)
1
0 to 70 (LD)
0 to 600
0.1
20 to 150 (ND)
0.1
20 to 100 (LD)
Page
9-5-5
9-5-1
8-1-5
9-5-6
9-7-2
9-7-11
9-7-11
9-7-2
9-7-11
9-7-11
9-7-2
-