Temporarily Changing RUN Command Input Source

 How to temporarily change the RUN command input source to the RUN key on the keypad?
Q
 How to temporarily change the RUN command input source to the input signals from the control
circuit terminal block?
 When the "Force operation [F-OP]" input terminal is turned on, the RUN and the STOP/RESET
A
keys on the keypad can be used to issue operation start and stop commands, having priority
over the RUN command input source specified by the "RUN command input source selection
*1
[A002]
".
 When the "Force terminal [F-TM]" input terminal is ON, the [FW]/[RV] terminals or the 3-wire
control function ([STA]/[STP]/[F/R]) terminals on the control circuit terminal block can issue
operation start and stop commands, having priority over the RUN command input source
specified by the "RUN command input source selection [A002]
"Force operation [F-OP]" / "Force terminal [F-TM]" operation
RUN key on the keypad
[FW]/[RV] terminals or 3-wire
[STA]/[STP]/[F/R] terminals on
the control circuit terminal
Configuration of " RUN command
input source selection [A002]
(All functions not assigned to input terminals [1] to [7] are turned off.)
Code
[C001]
Input terminal
to
function
[C007]
*1. "2nd-motor control [SET]" target parameter. The second control parameter is also subject to setting.
 When the [F-OP] or [F-TM] input terminals are ON, the frequency command input source
!
changes to the parameter setting from the keypad or analog input from the control circuit
terminal. For details, refer to "9.2.14 Temporarily Changing the Frequency Command Input
Source".
 When the [F-OP] or [F-TM] terminals are ON/OFF during inverter operation, the inverter will
stop. To restart operation, the RUN command must be turned off and on again.
 If the [F-OP] and [F-TM] terminals are turned on at the same time, the [F-OP] terminal is given
priority.
*1
", etc.
Item
Force operation [F-OP]:
When this terminal is ON, the RUN command and frequency
command input source are switched to the keypad.
Force terminal [F-TM]:
When this terminal is ON, the RUN command and frequency
command input source are switched to the control circuit
terminal block.
9-1-7
Inverter Functions
*1
".
Force
operation
Force terminal
[F-OP] (31)
[F-TM] (51)
ON
ON
OFF
OFF
Description
RUN
command
Data
31