Driving with Limited Torque

 How to limit output torque to prevent it from becoming excessively large?
Q
 How to set a stopping point so that the system stops when the end point is reached?
 To enable the torque limit function during speed control, assign the "Torque limit enable [TL]"
A
terminal to the input terminal and turn it on. Set the torque limit input source in "Torque limit
selection [b040]".
 The "Torque limited [TRQ]" assigned to the output terminal is ON while the above torque limit
function is in operation.
 If the "Torque limit enable [TL]" terminal is not assigned to an input terminal, the torque limit set
!
by "Torque limit selection [b040]" is always enabled.
 If the "Torque limit enable [TL]" terminal is assigned to an input terminal and OFF, the torque
limit is disabled.
 The motor may fail to start and the overload protection may trigger when using the torque limit
function at low speeds. In this case, use the overload restriction function
([b021]/[b221]/[b024]) together. For details, refer to "9.9.1 Restriction to Avoid Overload".
Code
[d012]
Output torque monitor
[b040]
Torque limit selection
Torque limit 1
[b041]
(Forward drive)
Torque limit 2
[b042]
(Reverse regenerative)
Torque limit 3
[b043]
(Reverse drive)
Torque limit 4
[b044]
(Forward regenerative)
Torque limit LADSTOP
[b045]
selection
[C001]
to
Input terminal function
[C007]
[C021]
Output terminal
[C022]
function
[C026]
Item
Monitors the estimated output torque value.
Specified for each of the four quadrants
individually.
Specified by the combination of [TRQ1]/[TRQ2]
terminals.
Specified by analog voltage input from the [Ai1]
terminal.
Specified from the option board.
Sets the torque limit value.
When [b040] is set to "4 quadrant individual setting
(00)", forward drive/reverse regenerative/reverse
drive/ forward regenerative are set individually.
When [b040] is set to "Switched by terminal
[TRQ1]/[TRQ2] (01)", the limit value specified for
the terminal input combination is applied to all four
quadrants.
Disable
Enable:
Temporarily suspend frequency deceleration
during torque limit operation.
Torque limit enable [TL]:
Enables/disables the torque limit function.
Torque limit selection bit 1/2 [TRQ1]/[TRQ2]:
When [b040] is set to " Switched by terminal
[TRQ1]/[TRQ2] (01)", the torque limit is specified
using this signal combination.
Torque limited [TRQ]:
This signal turns ON while the torque limit
function is in operation.
9-6-2
Inverter Functions
Description
Data
-200 to +200 (%)
00
01
02
03
0 to 200% /
no (Disable)
00
01
40
41/42
10