Hitachi WJ200-001SF Manual

Hitachi WJ200-001SF Manual

Wj200 series
Hide thumbs Also See for WJ200-001SF:

Advertisement

Pursuing the Ideal Compact Inverter
Pursuing the Ideal Compact Inverter
Series
Designed for excellent performance and user friendliness
Stöwer Antriebstechnik GmbH, Enneststrasse 3, 51702 Bergneustadt, tel: 02261-40970, Fax: 02261-41309

Advertisement

Table of Contents
loading

Summary of Contents for Hitachi WJ200-001SF

  • Page 1 Pursuing the Ideal Compact Inverter Pursuing the Ideal Compact Inverter Series Designed for excellent performance and user friendliness Stöwer Antriebstechnik GmbH, Enneststrasse 3, 51702 Bergneustadt, tel: 02261-40970, Fax: 02261-41309...
  • Page 2 WJ200 Output Frequency Output Frequency • Frequency commanded by the inverter: 0.5Hz. • Motor: Hitachi's standard 3-phase 5.5kW 4-pole totally enclosed type motor. PM + Dedicated Controller * WJ200: 5min , Previous model: 13min *Turn off this function for lifting equipment.
  • Page 3 A serial RS-485 Modbus/RTU port is standard. The WJ200 can Easy selection of displayed parameters program created with Hitachi's EzSQ software. User program can to Machinery Directive of Europe. Shuts down the inverter by communicate via DeviceNet, CompoNet, PROFIBUS and CANopen ●...
  • Page 4: Standard Specifications

    11.5 *1: The applicable motor refers to Hitachi standard 3-phase motor (4p). When using other motors, care must be taken to prevent the rated motor current (50/60Hz) from exceeding the rated output current of the inverter. *2: The output voltage varies as the main supply voltage varies (except when using the AVR function). In any case, the output voltage cannot exceed the input power supply voltage.
  • Page 5: General Specifications

    This value decreases when operating beyond 50Hz. If a large regenerative torque is required, the optional regenerative braking unit and a resistor should be used. *6: The frequency command is the maximum frequency at 9.8V for input voltage 0 to 10VDC, or at 19.6mA for input current 4 to 20mA. If this characteristic is not satisfactory for your application, contact your Hitachi representative.
  • Page 6 Dimensions [Unit: mm(inch)] • WJ200-001LF – 007LF • WJ200-055LF Inches for reference only • WJ200-001SF – 004SF • WJ200-075LF 140 (5.51) • WJ200-055HF 68 (2.68) Ø6 (0.24) • WJ200-075HF Ø4.5 (0.18) WJ200 INVERTER RUN PWR WJ200 INVERTER RUN PWR Hz ALM...
  • Page 7: Operation And Programming

    Operation and Programming Operation Panel WJ200 Series can be easily operated with the digital operator provided as standard. ( 4 ) Run LED ( 1 ) POWER LED ON when inverter is in RUN mode. ON (Green) while the inverter is receiving input power.
  • Page 8: Terminal Description

    Terminal ( Arrangements / Functions Terminal Description Symbol Terminal Name Symbol Terminal Name R/L1, S/L2, T/L3 Main power supply input terminals P/+, RB External braking resistor connection terminals U/T1, V/T2, W/T3 Inverter output terminals P/+, N/- External braking unit connection terminals PD/+1, P/+ DC reactor connection terminals Ground connection terminal...
  • Page 9: Hardware Switches

    Hardware Switches a Termination resistor selection switch Switch Name Switch Name Description Termination resistor for the RS-485 a Termination resistor selection switch communication port. (Default) WJ200 has a built-in 200Ω resistor activated by a DIP switch. b Safe stop function selection switch To enable the Safe stop function, set the b Safe stop function...
  • Page 10: Function List

    Function List If a desired parameter is not displayed, check the setting of function "b037"(function code display restriction). To display all parameters, specify "00" for "b037". [ ○ = Allowed × = Not parmitted] Setting During Change During Default Code Function Name Setting Range Operation...
  • Page 11 [ ○ = Allowed × = Not parmitted] Setting During Change During Default Code Function Name Setting Range Operation Operation Setting (allowed or not) (allowed or not) A019 Multi-speed operation selection 00 (Binary mode) / 01 (Bit mode) × × A020 Multi-speed 0 setting 0.00 / "start frequency"...
  • Page 12 Function List [ ○ = Allowed × = Not parmitted] Setting During Change During Default Code Function Name Setting Range Operation Operation Setting (allowed or not) (allowed or not) A085 Operation mode selection 00 (normal operation), / 01 (energy-saving operation) ×...
  • Page 13 [ ○ = Allowed × = Not parmitted] Setting During Change During Default Code Function Name Setting Range Operation Operation Setting (allowed or not) (allowed or not) 00 (disabled) / 01 (enabled during acceleration and constant-speed operation) / b021 Overload restriction operation mode ×...
  • Page 14 Function List [ ○ = Allowed × = Not parmitted] Setting During Change During Default Code Function Name Setting Range Operation Operation Setting (allowed or not) (allowed or not) 00 (starting with 0 Hz) / b088 Restart mode after FRS 01 (starting with matching frequency) / ×...
  • Page 15 [ ○ = Allowed × = Not parmitted] Setting During Change During Default Code Function Name Setting Range Operation Operation Setting (allowed or not) (allowed or not) 00 (FW: Forward Run) / 01 (RV: Reverse RUN) / 02 (CF1: Multispeed 1setting) / 03 (CF2: Multispeed 2 setting) / 04 (CF3: Multispeed 3 setting) / C001 05 (CF4: Multispeed 4 setting) / 06 (JG: Jogging) / 07 (DB: external DC braking) /...
  • Page 16 Function List Setting During Change During Default Code Function Name Setting Range Operation Operation Setting (allowed or not) (allowed or not) 00 (output during acceleration/deceleration and constant-speed operation) / C038 Output mode of low load detection signal × ○ 01 (output only during constant-speed operation) Rated current C039 Low load detection level...
  • Page 17 00 (disabled auto-tuning) / 01 (auto-tuning without rotation) / H001 Auto-tuning Setting × × 02 (auto-tuning with rotation) H002 Motor data selection × × 00 (Hitachi standard data) / 02 (auto-tuned data) H202 Motor data selection, 2nd motor × × H003 Motor capacity × × Factory set 0.1 / 0.2 / 0.4 / 0.55 / 0.75 / 1.1 / 1.5 / 2.2 / 3.0 / 3.7 / 4.0 / 5.5 / 7.5 / 11.0 / 15.0 / 18.5 [kW]...
  • Page 18 Function List [ ○ = Allowed × = Not parmitted] Setting During Change During Default Code Function Name Setting Range Operation Operation Setting (allowed or not) (allowed or not) P033 Torque command input selection 00 (O terminal) / 01 (OI terminal) / 03 (digital operator) / 06 (Option) ×...
  • Page 19: Protective Functions

    Protective Functions Name Cause(s) Error Code Over-current event while at constant speed E01. The inverter output was short-circuited, or the motor shaft is locked or has a heavy load. Over-current event during deceleration E02. These conditions cause excessive current for the inverter, so the inverter output is turned OFF. Over-current event during acceleration E03.
  • Page 20: Connecting Diagram

    Connecting Diagram Source Type Logic R/L1 U/T1 S/L2 V/T2 T/L3 Power source, 24VDC W/T3 3-phase or 1-phase, Motor per inverter model Short bar Using source logic of Short bar external machine PD/+1 output and/or external Remove the jumper power supply, only when connecting please refer to P24.
  • Page 21 Sink Type Logic R/L1 U/T1 S/L2 V/T2 T/L3 Power source, 24VDC W/T3 3-phase or 1-phase, Motor Short bar per inverter model Short bar Using source logic of external machine output and/or external PD/+1 power supply, please refer to P24. Remove the jumper only when connecting the DCL.
  • Page 22 Connection with Input Terminals Using Internal Power Supply of the Inverter Using External Power Supply (Please remove the short bar.) Short bar 24VDC 24VDC DC24V Hitachi EH-150 series PLC Hitachi EH-150 series PLC Output Module EH-YT16 Output Module EH-YTP16 Inverter Inverter 24VDC 24VDC...
  • Page 23 Wiring and Accessories Power Supply Motor Output Wiring Fuse Input Inverter (UL-rated, Voltage Model Power Lines Signal Lines class J, 600V) WJ200-001SF WJ200-002SF AWG16 / 1.3mm ° C only) 1-phase 0.55 WJ200-004SF 200V ° 0.75 WJ200-007SF AWG12 / 3.3mm C only) WJ200-015SF AWG10 / 5.3mm...
  • Page 24: For Correct Operation

    Therefore, carefully make selection and settings by checking the mechanical strength of the motor and connected machines. Consult the motor manufacturer when it is necessary to drive a standard (general-purpose) motor above 60 Hz. A full line of high-speed motors is available from Hitachi.
  • Page 25 [Main power supply] In the following examples involving a general-purpose inverter, a large peak current flows on the main power supply side, and is able to destroy the converter module. Where such situations are foreseen or the connected equipment must be highly reliable, install an AC reactor between the power supply and the inverter.
  • Page 26 Printed in Japan ( H ) SM-E265P 0910 Stöwer Antriebstechnik GmbH, Enneststrasse 3, 51702 Bergneustadt, tel: 02261-40970, Fax: 02261-41309...

Table of Contents